7
6 commIssIoNINg
6.1 Setting Fan speed
The speed of the unit can be adjusted during installation according to required ventilation rate.
Figure 6.a
below shows performance curves (for supply air and extract air) at different settings of the 0-10V signal to the motors.
Airflow and consumption refer to one single motor.
Table 6.b
indicates the sound level at the different speed.
curve
speed
%
W
max
m
3
/h
max
A (min)
20
9
51
B
37
33
124
C
53
85
196
D
58
108
219
E
67
175
270
F
84
265
305
G (max)
100
335
352
Intake curve according to Regulation
1253/2014 (ErP).
0
50
100
150
200
250
300
350
400
450
500
550
600
0
50
100
150
200
250
300
350
400
A
B
C
D
E
F
G
Static Pressure - Pa
Airflow - m
3
/h
Data of the enthalpic heat exchanger
Test conditions:
Indoor air 25°C and 50% RH
External air 5°C 70% RH
0
10
20
30
40
50
60
70
80
90
100
0
50
100
150
200
250
300
350
Curva di efficienza termica
Curva di efficienza igrometrica
Airflow - m
3
/h
Efficiency - %
Thermical efficiency curve
Hygrometric efficiency curve
100%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1 K
2 K
4 K
8K
Tot
@3m
Intake
83
65
70
73
62
58
53
47
84
51
Supply
81
65
65
66
57
51
42
33
81
45
Extract
80
63
66
68
60
54
45
34
78
47
Exhaust
78
65
70
71
62
59
53
45
80
50
Breakout
81
69
67
69
62
56
48
36
82
48
80%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1 K
2 K
4 K
8K
Tot
@3m
Intake
73
61
67
69
59
56
50
43
75
47
Supply
72
61
63
65
56
50
41
31
74
43
Extract
73
60
63
65
57
51
42
31
74
44
Exhaust
73
61
66
67
58
55
49
41
75
46
Breakout
71
64
62
67
59
53
45
33
74
45