7
2014/35/EC Low Voltage Directive (LVD)
2014/30/EC Electromagnetic Compatibility (EMC),
in conformity with the following standards:
Electrical Safety: EN60335-1(2012)+A11+A13; EN 60335-2-80(2003)+A1+A2.
Electromagnetic Compatibility: EN 55014-1(2017); EN 55014-2(2015); EN 61000-3-
2(2014); EN 61000-3-3(2013).
stanDarD conForMitY
Operation
: connected according to the diagram in fig. 13B, after the light is switched
on, the fan activates with a delay of max 1.5 seconds. After the light is switched off, the
fan continues to function for a pre-set period of time.
With huMiDistat & tiMer
The fan is equipped with a humidity detector, whose threshold is adjustable from 50%
to 95% Relative Humidity, and with a timer which is adjustable from aprox. 1 minute to
25 minutes via corresponding trimmer (fig. 14D).
Turn the trimmer HY completely clockwise and the humidistat function is deactivated.
Automatic humidistat operation: connected according to the diagram in fig. 13D, when
the percentage of Relative Humidity exceeds the pre-set intervention threshold, the
fan starts up automatically. When the percentage of Relative Humidity goes below the
threshold, the fan continues to function for a pre-set period of time.
Operation with switch connection: connected according to the diagram in fig. 13D,
after the light is switched on, the fan activates with a delay of aprox. 1.5 seconds. After
it is switched off, the fan continues to function for a pre-set period of time.
Operation via pull cord switch (HTPC version): connected according to the diagram in
fig. 14C. By switching on, the fan activates with a delay of aprox. 1.5 seconds. After
switching off, the fan continues to function for a pre-set period of time.
attention
: When the relative humidity level is higher than the pre-set threshold,
automatic operation with humidistat has priority over manual operation, or rather the
fan cannot be stopped via switch.