Ground Resistance Testers Models 6422 & 6424
2.3.3 Grounding Resistance Measurement
For the first grounding resistance test, we recommend starting with the 62 %
distance.
1. Place the H and S rods in a line with the grounding electrode under test.
The distance between the S rod and the grounding electrode must be
approximately 62 % of the distance (d) between the H rod and the grounding
electrode. (To avoid electromagnetic interference, we recommend using
the full length of the cables, placing them several inches apart and avoiding
loops).
2. Connect the cables to the H and S terminals.
3. Power down the installation and isolate the ground under test from other
ground systems and connections.
4. Connect the E terminal to the grounding electrode to be tested.
5. Press
TEST
to take a measurement in automatic mode.
The
TEST
button blinks red, then the measurement is displayed. It
remains frozen (
HOLD
) until you press
TEST
again.
(Model 6424)
R
H
and U
SE
values are displayed.