Power & Energy Logger Model PEL 105 - Quick Start Guide
3-Phase 4-Wire Open ∆
• VE/GND test lead to ground
• VN test lead to neutral (N)
• V1 test lead to L1
• V2 test lead to L2
• V3 test lead to L3
• IN probe to neutral
• I1 probe to L1
• I2 probe to L2
• I3 probe to L3
3-Phase 4-Wire ∆
(3P-4W∆)
• VE/GND test lead to ground
• VN test lead to neutral (N)
• V1 test lead to L1
• V2 test lead to L2
• V3 test lead to L3
• IN probe to neutral
• I1 probe to L1
• I2 probe to L2
• I3 probe to L3
L1
L2
L3
N
V1 V2 V3 N
I1
I2
I3
N
L2
L1
L3
L1
L2
L3
N
V1 V2 V3 N
I1
I2
I3
N
L2
L1
L3
DC 2-Wire
(dC-2W)
• VE/GND test lead to ground
• VN test lead to the common conductor.
• V1 test lead to con1
• IN probe to the common conductor
• I1 probe to con1
DC 3-Wire
(dC-3W)
• VE/GND test lead to ground
• VN test lead to the common conductor
• V1 test lead to con1
• V2 test lead to con2
• IN probe to the common conductor
• I1 probe to con1
• I2 probe to con2
+1
-
V1 V2 V3 N
I1
I2
I3
+1
+2
-
V1 V2 V3 N
I1
I2
I3