Power Quality Analyzer PowerPad
®
IV Model 8345
35
Press
to configure the Trend mode
Select the quantities to record
The frequency (Hz) is always selected.
For more information about these quantities, refer to the glossary in § 20.10.
Red quantities are incompatible with the configuration and cannot be recorded.
Pages 2 and 3 concern the recording of harmonics. For each of these quantities,
you can select the orders of the harmonics to record (between 0 and 63) and, if
desired, select to record the odd harmonics only.
Levels of harmonics of order 01 will be displayed only when they concern values
stated in %r.
Press the
button to configure the recording’s length, setup, recording
period, and name
For
Duration
, enter the trend recording’s duration between 1 min and 2 hr
For
Set-up
, choose a configuration from four user-defined configurations
For
Period
, choose the recording period from the 19 available options
between 200 ms and 2 h
For
Name
, enter the recording’s name (up to 8 characters long) using
capital letters (A-Z), numbers (0-9), and symbols (&, _, and -)