Power Quality Analyzer PowerPad
®
IV Model 8345
95
Measurement
Measurement Range
without ratio
(with unity ratio)
Display
Resolution
(unity ratio)
Max Intrinsic
Error
Min
Max
RMS
Current
Measurement
(1)
SR193 clamp
MR193 clamp
1.000 A
47.09 A
4 digits
±(0.5 % + 200 mA)
47.10 A
566.0 A
4 digits
±0.5 %
(2)
566.1 A
1000 A
4 digits
±(0.5 % + 200 mA)
MN93 clamp
200.0 mA
9.429 A
4 digits
±(0.5 % + 20 mA)
9.430 A
113.0 A
4 digits
±0.5 %
(2)
113.1 A
200.0 A
4 digits
±(0.5 % + 200 mA)
SL261 clamp
(10 mV/A)
MN193 clamp
(100 A)
200.0 mA
4.709 A
4 digits
±(0.5 % + 20 mA)
4.710 A
56.60 A
4 digits
±0.5 %
(2)
56.61 A
100.0 A
4 digits
±(0.5 % + 200 mA)
SL261 clamp
(100 mV/A)
20.00 mA 353.9 mA
4 digits
±(0.5 % + 2 mA)
354.0 mA
4.240 A
4 digits
±0.5 %
(2)
4.241 A
10.00 A
4 digits
±(0.5 % + 10 mA)
MN193 clamp
(5 A)
5.000 mA 176.9 mA
4 digits
±(0.5 % + 2 mA)
177.0 mA
2.120 A
4 digits
±0.5 %
(2)
2.121 A
5.000 A
4 digits
±(0.5 % + 2 mA)
AmpFlex
®
193
MiniFlex
®
MA194-24-BK
(10 kA)
10.00 A
299.9 A
4 digits
±(0.5 % + 3 A)
300.0 A
3000 A
4 digits
±0.5 %
(2)
3001 A
10 000 A
4 digits
±(0.5 % + 3 A)
AmpFlex
®
193
MiniFlex
®
MA194-24-BK
(1000 A)
1.000 A
29.99 A
4 digits
±(0.5 % + 0.5 A)
30.00 A
300.0 A
4 digits
±0.5 %
(2)
300.1 A
1000 A
4 digits
±(0.5 % + 0.5 A)
AmpFlex
®
193
MiniFlex
®
MA194-24-BK
(100 A)
100.0 mA
2.999 A
4 digits
±(0.5 % + 100 mA)
3.000 A
30.00 A
4 digits
±0.5 %
(2)
30.01 A
100 A
4 digits
±(0.5 % + 3 A)
DC Current
Measurement
MR193 clamp
1 A
1300 A
(1)
4 digits
±(1 % + 1 A)
SL261 clamp
(10 mV/A)
200 mA
100 A
(1)
4 digits
±(1 % + 100 mA)
SL261 clamp
(100 mV/A)
20 mA
10 A
(1)
4 digits
±(1 % + 10 mA)
1. Total RMS value and RMS value of the fundamental
2. The intrinsic uncertainty of Class A is ±1 %