BREAKER
ୟഗ
IP54 Covers:
Each ME09 breaker is supplied with a Door Frame that provides the
installed device with an IP40 ra
Ɵ
ng. Op
Ɵ
onally an extra cover is
available providing an IP54 ra
Ɵ
ng.
Opera
Ɵ
ons Counter:
Provides local record of the cumula
Ɵ
ve number of complete
breaker closing opera
Ɵ
ons.
Cable Interlocking Devices:
A set of devices that are available for
Į
xed and/ or drawout
devices. They allow the interlocking of two or three ME09
breakers in
Į
xed or drawout pa
Ʃ
ern. Each mdevice has two
parts, a factory mounted interlocking mechanisms and two or
more separately available cables.
Bell Alarm Contact:
A changeover contact that once
ĮƩ
ed to the breaker indicates if
the breakers has tripped on one of it's protec
Ɵ
ve func
Ɵ
ons
(Electronic Trip Unit).
An interface on the Trip Unit front face allows a Manual or
Automa
Ɵ
c breakers reset. The Bell Alarm Contact will only
permanently change posi
Ɵ
on when the Trip Unit is in Manual
mode. The Trip unit has a func
Ɵ
on (trip reason and event
logger ) that allows the user to establish why the breaker has
tripped.
Spring Charged and Ready to Close Contacts:
A breaker with electrical charging mechanism can be equipped
with one or two indica
Ɵ
on contacts.
The
Į
rst the Spring Charged Contact simply does as indicated
and is supplied with the standard Motor Opera
Ɵ
ng Mechanism.
The second, the ready to close indica
Ɵ
on, op
Ɵ
onally replaces
the Spring Charged Contact.
It only moves posi
Ɵ
on when the following condi
Ɵ
ons are met:
- The circuit breaker is open
- The closing springs are charged
- The circuit breaker is not locked/interlocked in open posi
Ɵ
on
- There is no standing closing order
- There is no standing opening order
Both contacts have a 1NO con
Į
gura
Ɵ
on.
1.1.3 Storage
Store circuit breakers and casse
Ʃ
es in a clean, dry loca
Ɵ
on in
their original packaging.
NF1:ဣଚگუഘୟഗ