17
PD201709 AEG GRID-TIED THREE-PHASE SOLAR INVERTER (4-10 kW) V.1-17 EN
17
3.2.3 Connection cables
Below is an overview of the cable specifications:
Model
DC side
AC side
Cross-section
(length ≤50m)
mm²
Cross-section
(length >50m)
mm²
Mini cross-section
mm²
L
N/PE
AS-IC01-4000 / AS-IC01-4000-2 / AS-IC01-5000 /
AS-IC01-5000-2/ AS-IC01-6000-2 / AS-IC01-8000-2
/ AS-IC01-10000-2
4
6
4
Table 9: Cable specifications
3.2.4 Miniature circuit breakers
It is highly recommended to install circuit breakers or fuses at the DC input and AC output to ensure safe installation
and operation.
In order to protect the PCE, user and installer, external DC and AC circuit breaker shall be equipped
at the end-use application. The wiring shall follow local electric codes. Choose proper cable for power
input and output lines. Input and output cables shall be solar cables suitable for outdoor use.
Breaker specifications:
Model
DC input
AC output
Recommended DC breakers
(optional for length >100m)
Recommended AC breakers
AS-IC01-4000 / AS-IC01-4000-2 / AS-IC01-5000 /
AS-IC01-5000-2
DC1000V, C20A, 4P
AC400V, C20A, 4P
AS-IC01-6000-2 / AS-IC01-8000-2 /
AS-IC01-10000-2
DC1000V, C20A, 4P
AC400V, C20A, 4P
Table 10: Breaker specifications
3.3 Mechanical installation
As the installation place can be chosen among different construction materials, the inverter can be installed by different
mounting methods. Taking the typical installation environment as the example, the manual describes how to install the
inverter on concrete wall.