--------------------------------------------------------------------------16/21------------------------------------------------------------------------------------
TOR – Maximal reading time
TOR is a timing parameter of the reader. It is used in operation mode 2 to limit the reading attempts. The
maximal time for one reading cycle is TOR * TB. The timing parameter TB (Time base) has the default value
100 ms. One reading cycle can consist of several single reading attempts, until one is successful, or TOR time
is expired. From external one reading cycle looks like one single reading.
Input format:
TOR <SP> Parameter <CR>
Parameter:
Parameter
Function
2
Limitation of the reading attempts to approx.2 times TB
3
Limitation of the reading attempts to approx.3 times TB
...
999
Limitation of the reading attempts to approx. 999 times TB
Output (Example):
2 <CR>
BUZ – Buzzer
The successful reading of a transponder can be shown by an acoustic signal. The buzzer is activated or deac-
tivated with the BUZ command.
Input format:
BUZ <SP> Parameter <CR>
Parameter:
Parameter
Function
0
Buzzer off
1
Buzzer on, output in Good and Bad Read case
2
Buzzer on, Good Read indication only (Default value)
Output (Example):
2 <CR>