AEC UPS IST7 10-30 kVA
User Manual
A Technical Specifications
73
Model Index
10kVA 20kVA 30kVA
Frequency (Hz)
When mains normal, it tracks the bypass input;
When mains abnormal, it tracks the frequency of the UPS in the
range of 50
±
0.1% or 60
±
0.1%.
Three-phase phase error
With three-phase rated balance resistive load
≤
1
°
Wave form distortion (THDv)
Resistive full load
≤
1%; non-linear load
≤
4%
Bypass inversion switch time
Synchronization
<
0ms; Unsync:
<
15ms
System efficiency
96
%
Overload capacity
Inverter overload capacity:
When the load less than 105
%
rated load, it runs normally.
When the load in the range of 105%~115
%
rated load, it will turns
to bypass 60min later.
When the load in the range of 116%~130
%
rated load, it will turns
to bypass 10min later.
When the load in the range of 131%~150
%
rated load, it will turns
to bypass 1min later.
When the load in the range of 151%~250
%
rated load, it will turns
to bypass 200ms later.
When the load greater than 251
%
rated load, it will turns to bypass
10ms later.
Bypass overload capacity:
When the load less than 130
%
rated load, it runs normally.
When the load in the range of 131%~150
%
rated load, it can
maintain 10min.
When the load greater than 150
%
rated load, it can maintain 100ms.
Current-equalized precision
≤
5%
Output DC component
-200mV~+200mV