1.3
Page 18
MPC-
143. User’s Manual
Figure 19.
“Modbus devices” tab. Modbus RTU client parameters
list configuration
NOTE: Maximum number of requests per each Modbus RTU Client is
50
NOTE: There exist 2 Modbus RTU clients. In case that both must work
together 2 different UARTs must be used, one per each Modbus RTU
client.
In “Current values” window it is possible to check the received information through the
Modbus RTU client. With this screen it is possible to check the correct performance of
Modbus devices.
Figure 20.
“Modbus devices” tab. Current values
6.6 Communication >Data transfer
Data collected by MPC-143 can be sent in a CSV file through the configuration of an FTP
client inside the controller (if supported by specific model). This file is, thus, sent to a
remote FTP server properly defined as shown below. FTP Configuration must be done in
two steps:
1. Define CSV file structure: Go to
Communication>Data transfer>Common
parameters>
and configure the following parameters: