EKI-6333AC-M12 Series support 24 to 110 V
DC
. Dual power inputs are supported
and allow you to connect a backup power source.
Figure 2.11 Power Wiring for EKI-6333AC-M12 Series
2.2.6.2
Considerations
Take into consideration the following guidelines before wiring the device:
The Terminal Block (CN1) is suitable for 12-24 AWG (3.31 - 0.205 mm
2
). Torque
value 7 lb-in.
The cross sectional area of the earthing conductors shall be at least 3.31 mm
2
.
Calculate the maximum possible current for each power and common wire.
Make sure the power draw is within limits of local electrical code regulations.
For best practices, route wiring for power and devices on separate paths.
Do not bundle together wiring with similar electrical characteristics.
Make sure to separate input and output wiring.
Label all wiring and cabling to the various devices for more effective
management and servicing.
2.2.6.3
Grounding the Device
P2 P1
Chassis
GND
(pane)
One DC Supply
P2 P1
Chassis
GND
(pane)
Dual DC Supplies
Single DC Power
Redundant DC Power
Note!
Routing communications and power wiring through the same conduit
may cause signal interference. To avoid interference and signal
degradation, route power and communications wires through separate
conduits.
Caution!
Do not disconnect modules or cabling unless the power is first switched
off.
The device only supports the voltage outlined in the type plate. Do not
use any other power components except those specifically designated
for the device.
Caution!
Before connecting the device properly ground the device. Lack of a
proper grounding setup may result in a safety risk and could be
hazardous.
Caution!
Do not service equipment or cables during periods of lightning activity.