Portable Chiller: MGD-15W-ADV-02
Page: 37
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
To Process
50°F
S etpoi nt : 50°F
Circulating
To Process
50°F
S etpoi nt : 50°F
Circulating
July
To Process
50°F
S etpoi nt : 50°F
Circulating
To Process
50°F
S etpoi nt : 50°F
Circulating
To Process
50°F
S etpoi nt : 50°F
Circulating
consulting the Factory:
LP Cut Out, LP Cut In, LP Start Up Delay, LP Run
Delay, HP Cut Out, Secondary Pump, Chiller Type
,
Cooling Source.
B.
Set Date
1.
Set the date by selecting the Set Date option from the Machine Menu. Using the
Up and Down Arrow keys to select the month, day and year. Use the Select and
Back Buttons to advance between Month, Day and Year.
C.
Set Time.
1.
Set the time by selecting the Set Time option from the Machine Menu. Using the
Up and Down Arrow keys to select the hour, minute and seconds. Use the Select
and Back Buttons to advance between Hour, Minute and Seconds.
D.
Minimum Setpoint.
This parameter sets the lowest permissible setpoint temperature.
The factory default is 48°F. The range is from 0°F - 90°F.
1.
For Minimum Setpoints below 48°F.
A warning is displayed when a minimum
setpoint below 48°F is entered. The warning ensures the operator is aware an
appropriate mixture of water/glycol is circulating to prevent freezing.
2.
After a minimum setpoint below 48°F is selected, a caution display will appear
when reducing the operating setpoint below 48°F. The warning must be
acknowledged before the change is made by pressing the Select button.
3.
For Minimum Setpoints 48°F and above.
From the Machine Menu, advance
to the Minimum Setpoint screen to enter the minimum setpoint. Confirm the
selection with the Select Button.
14
: 42 : 42
50°F
ATTENTION