Portable Chiller: MGD-15W-ADV-02
Page: 30
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
To Process
50°F
S etpoi nt : 50°F
Circulating
To Process
50°F
S etpoi nt : 50°F
Circulating
To Process
50°F
S etpoi nt : 50°F
Circulating
control, when the first and fourth control status indicators are larger than
the others the compressor is running and the capacity control feature is
engaged indicating that the chiller capacity is greater than the cooling
demand.
d.
The middle two status indicators are not used for chillers using single
digital scroll compressors or fixed scroll compressors with hot gas
bypass.
e.
Refer to Section 8.6 for other details concerning Status Indicators.
7.
Suction
indicates the refrigerant suction pressure, sometimes referred to as 'low'
or 'evaporator' pressure.
8.
Discharge
indicates the refrigerant discharge pressure, sometimes referred to as
'high' or 'head' pressure.
9.
To Process
indicates the process cooling fluid (water or water/glycol) pressure.
10.
When the compressor is turned off, the instrument will wait 3 minutes before
turning it back on regardless of the To Process temperature or Setpoint.
If a low pressure or optional low flow fault has occurred, the control will attempt
to turn the compressor back on after 3 minutes. If the fault condition remains, the
compressor will not restart and the control will retry after 1 minute. The sequence
will repeat 3 times then the system will lock-out and the unit must be powered off/
on to restart the unit.
If a high pressure fault occurs the fault must be acknowledged by pressing the
start button before the system will attempt to restart.
14°F
Circulating
14°F
Discharge 300 PSI
14°F
Circulating
14°F
14°F
Circulating
14°F
To Process
44 PSI