3.5
Instrument: Setpoints menu
A.
Under the Setpoints menu item, the values for the Process Setpoint, Hi Deviation, Low
Deviation and Low Flow can be set or changed. Digital flow rate display is an option and
may not be included on your machine.
B.
Process Setpoint.
Use the Up or Down buttons to change the process setpoint.
1.
The factory setpoint is 14°F. The straight water range is from 48°F to 90°F or 9° -
32°C.
2.
Once acknowledged, the unit will control to the new setpoint temperature. Press
the Back button repeatedly to return to the Setpoints screen or press the home
button to return to the Home screen.
C.
Hi Deviation.
The High Deviation value programs the controller to sound the alarm if the
process temperature exceeds the set difference from setpoint. For example, Hi Deviation
= 10°F, Setpoint = 50°F. Hi deviation alarm will sound if the temperature reaches 60°F.
1.
The factory default is 10°F. The range for the Hi Deviation is from 0°F - 50°F.
2.
With set points above 50°F, the maximum Hi Deviation setting should be no
more than 100°F minus set point. For example, with a 70°F set point the High
Deviation should not be set more than 30°F.
14°F
10°F