10
hours and 59 minutes. Ex. An on time of 15 minutes and an off time of 15 minutes will cycle
the pump on 15 minutes and off 15 minutes repeatedly.
2.
Pulse Timer and Flowmeter Input -
See Menu Map on Page 11
Pulse timer allows the pump to run based on signals from an external dry contact switch closure.
Incoming pulse rate must not exceed 1,800 pulses per minute. There are four selections for a
pump with this option selectable on the
MENU
page
EXT=
which is short for external.
Press
to select the desired external pulse function from the selections below. Press the ENTER key
to set the desired pulse function.
With screen showing
Timer: MLTIPL BY
the pump strokes based on multiplying each
incoming pulse by 1 to 9999. With the screen set for
Timer: DIVIDE BY
it strokes based
on dividing each in coming pulse. For example, if the pump is told to divide by five it will
count five incoming external pulses and then stroke one time.
The pump will store strokes (a maximum of 65,000 divided by the set multiply factor) to be
made if contacts come in faster than the pumps stroking. If the stored number of strokes
exceeds the maximum any additional strokes are lost.
3.
Biocide or Event Timer -
See Menu Map on Page 11
Biocide or event timers allow the pump to feed chemical based on a 28-day timer for the daily,
weekly, or monthly addition of chemicals. The unit has four programmable timers labeled P1,
P2, P3, and P4.
VII. Set-Up Menus
0
hours and 59 minutes. Ex. An on time of 5 minutes and an off time of 5 minutes will cycle
the pump on 5 minutes and off 5 minutes repeatedly.
2.
Pulse Timer and Flowmeter Input -
See Menu Map on Page 11
Pulse timer allows the pump to run based on signals from an external dry contact switch
closure. There are four selections for a pump with this option selectable on the
MENU
page
EXT=
which is short for external.
Press
to select the desired external pulse function from
the selections below. Press the ENTER key to set the desired pulse function.
With screen showing
Timer: MLTIPL BY
the pump strokes based on multiplying each
incoming pulse by to 9999. With the screen set for
Timer: DIVIDE BY
it strokes based
on dividing each in coming pulse. For example, if the pump is told to divide by five it will
count five incoming external pulses and then stroke one time.
The pump will store strokes (a maximum of 65,000 divided by the set multiply factor) to be
made if contacts come in faster than the pumps stroking. If the stored number of strokes
exceeds the maximum any additional strokes are lost.
3.
Biocide or Event Timer -
See Menu Map on Page 11
Biocide or event timers allow the pump to feed chemical based on a 28-day timer for the daily,
weekly, or monthly addition of chemicals. The unit has four programmable timers labeled P,
P2, P3, and P4.
VII. Set-Up Menus
125 Strokes/Min
Reset Counter? N
Model Axxx
MENU MAP
Use the ARROW keys to change
options and the ENTER key to
continue to next menu item.
Software version 8.2.a
Prime ALM:020STR
Grayed out menu items are
available only when FloTracker
option is enabled.
FT: 003.33 ML/P