31
3.3.2.5 Device Text
This parameter shows the 26-character location text assigned to this device. For guidance on how to change
the text, refer to Section
3.3.2.6 Action
This parameter shows the action that will be performed when this device indicates an active (alarm) condition.
For example:
[Loop 1 Devices] <More>
Address Action Sensitivity O/P
001.0 FIRE SIGNAL DEFAULT
002.0 FIRE SIGNAL DEFAULT
002.1 NO ACTION
5
003.0 FIRE SIGNAL DEFAULT
Press the
✔
button to change the action assigned to this input device. A pop-up window is then shown on the
display from which an action can be selected.
[Select New Action]
FIRE SIGNAL .
PRE-ALARM
FAULT SIGNAL
Press the
buttons to scroll through the list of Actions and then press the
✔
button to confirm the change.
The display reverts to the device list showing the new action assigned to this device. Alternatively, press the
‘Esc’
button to cancel the changes and return to the device list display. The following Actions are available
(Additional actions are available on a PC)
Action
Description
Fire Signal
6
A Fire Alarm Condition will be generated whenever the input is active.
Pre-Alarm
A Pre-Alarm Condition will be generated whenever the input is active.
Fault Signal
A Fault Condition will be generated whenever the input is active.
Security
A Security Alert Condition will be generated whenever the input is active.
Record
A Record Entry will be stored in the Log whenever the input is active. This will be hidden from the panel
status display.
Create Alarm 1
An “Alarm 1” condition will be generated whenever this input is active.
Create Alarm 2
An “Alarm 2” condition will be generated whenever this input is active.
Create Alarm 3
An “Alarm 3” condition will be generated whenever this input is active.
Key Lock
Enables / Inhibits front panel controls (Disable, Mute, Reset etc.)
-
No Action is assigned to the input.
Control Signal
Allows control of Outputs without
displaying “Fault” or “Fire” or sounding buzzer
Acknowledge
Activation of the input acknowledges a Stage 1 Investigation Delay and invokes the Stage 2 Timer
LED Test
7
Activation invokes a test of the panel LED Indicators.
5
The action of the Heat sub-address of Multi-sensor, Heat and Heat ROR devices is fixed at NO ACTION and cannot be changed.
6
Fire Alarm Conditions are latched. By default, all other conditions are non-latching. The action for smoke and certain other detectors is
always fire and cannot be changed.
7
LED Test can only be configured using the PC Tool.
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for MX-4200V
Page 68: ...68 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 69: ...69 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 70: ...70 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Page 71: ...71 USER NOTES www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...