ElectraCOOL™ LA600
USER’S MANUAL
ADVANCED THERMOELECTRIC · PO Box 7091 · Nashua, NH 03060
Toll free: 1 (866) 665-5434
·
(603) 888-2467
·
fax: (603) 724-6740
·
e-mail: [email protected]
2
3.
PRODUCT HANDLING:
DO NOT OPERATE YOUR CHILLER BEFORE READING THIS MANUAL
Read
MSDS for the coolant used in your system and follow all safety precautions listed in the
MSDS prior to connecting the LA600 with coolant tubing or opening the fill cap as this could
result in contact with the coolant inside.
Before operating your new Chiller be certain that:
1. Unit is placed in the proper upright (vertical) position.
2. Liquid reservoir (and line to object cooled) is/are filled with coolant.
3. The chiller should have at least 12” free air space for air intake and exhaust.
4. Make sure that proper input voltage is supplied to the unit. In general US line
voltage is 115 VAC and Europe is 230 VAC but check with your facilities manger.
WARNING Electrical Shock Hazard
1.
PLUG UNIT INTO GROUNDED ELECTRICAL OUTLET
ONLY
2.
DO NOT OPERATE UNIT WITHOUT COOLANT IN THE SYSTEM
3.
MAKE SURE THAT LINE CIRCUIT BREAKER COINCIDES WITH
NAMEPLATE MAXIMUM FUSE RATING
Failure to follow the above precautions could result in electrical shock, fire,
personal injury or damage to the unit, and will void warranty.
4. TECHNICAL DATA: 115V & 230V Input Versions
Model
LA600-115
LA600-230
Input Voltage, VAC
115
230
Running Current, Amps
13.5
6.5
Frequency, Hz
50/60
50/60
Min. Ambient, °F/°C*
14 / -10
14 / -10
Max. Ambient, °F/°C*
122/50
122/50
Cooling Capacity Watt/
BtuH
**
800
/2728
800
/2728
Max. flow rate, GPM/LPM***
1.6/6.0
1.6/6.0
Max. pressure, PSI
14.7
14.7
Chiller fluid capacity, Gallons/ml
0.197/750
0.197/750
Control Temperature Range, * +14 to 113 °F (-10 to +45°C)
+14 to 113 °F (-10 to +45°C)
Control Accuracy, °F or °C
+/-0.1
+/-0.1
Reservoir Capacity, Gallons/ml
0.132/500
0.132/500
Heating Capacity, Max. Watts/
BtuH
600 /
2046
600 /
2046
*
For Higher or Lower Ambient or Control Temperatures consult
Advanced Thermoelectric.
** Capacity rating at 77°F/25°C for both ambient and outlet fluid temperature.
*** For more information see Pumping Capacity chart on the respective chiller
Technical Data Sheet.