10. TECHNICAL DATA
Type voltage
S..H1
230 Volt, 400 Volt, 500 Volt
– 57 % + 10 %;
S..HRL1
230 Volt – 15 % + 10 %;
> 99 V with additional 24 AC/DC elektronic power
400 Volt – 15 % + 10 %;
> 172 V with additional 24 AC/DC elektronic power
500 Volt – 15 % + 10 %;
> 215 V with additional 24 AC/DC elektronic power
Mains frequency
all models 47Hz to 63Hz;
=6Hz;
max. frequency change 5% per half wave
Load description
ohmic load
Operating modes
Name
Load signal, with digital set point = ON
1:1
all full wave (default setting)
1:2
every 2. mains full wave (DC free)
1:3
every 3. mains full wave (DC free)
1:5
every 4. mains full wave (DC free)
Digital set points inputs (connection signals)
The Thyro-S has 2 set point inputs. The set point inputs are safely
disconnected from the mains (SELV, PELV).
Set point 1:
Logic input 0-24 V R
i
> 3.3k
Ω
ON > 3 V
Set point 2:
System interface, connection from superset
automation system via optional bus module.
Relay outputs using type 1S...H RL1
Changer, contact material: AgSnO2 / Au plated
The relay can be used for low load circuits (> 5 V 20 mA), however
not if it has been pre-loaded by 230 V AC.
Maxiumum values: 250 V 6 A, 180 W, 1500 VA
Insulation strength 4 kV / 8 mm
Summary of Contents for Thyro-S 1S H 1 Series
Page 2: ...2...
Page 35: ...33 FIG 8 CONECTION DIAGRAM THYRO S 1S H 1...
Page 36: ...34 FIG 9 CONNECTING DIAGRAM 2X THYRO S 1S H 1...
Page 37: ...35 FIG 10 CONNECTING DIAGRAM THYRO S 1S H RL1...
Page 38: ...36 FIG 11 CONNECTING DIAGRAM 2X THYRO S 1S H RL1...
Page 44: ...42 11 DIMENSIONAL DRAWINGS THYRO S 1S 16H 30H THYRO S 1S 45H 60H...
Page 45: ...43 THYRO S 1S 100H THYRO S 1S 130H 170H...
Page 46: ...44 THYRO S 1S 280H...
Page 50: ......
Page 51: ......
Page 52: ......
Page 54: ......