Table 3‑8. Type Voltage 690 Volts ... Voltage Sequence Control (VSC)
Model
Type Current
(A)
Type Power
(kVA)
Dissipation
(W)
Current
Transformer
T1
Burden R
(Ω)
Fuse F1 (A)
Thyro-PX 1PX ... VSC2
80 H
55
125
100/1
1.2
100
200 HF
138
260
200/1
1.0
250
300 HF
207
360
300/1
1.0
350
500 HF
345
625
500/1
1.0
630
780 HF
538
910
1000/1
1.2
2x630
1400 HF
966
1900
1500/1
1.0
4x700
1850 HF
1380
3200
2000/1
1.0
4x900
2400 HF
1794
3450
3000/1
1.2
4x1400
Thyro-PX 1PX ... VSC3
80 H
55
125
100/1
1.2
100
200 HF
138
260
200/1
1.0
250
300 HF
207
360
300/1
1.0
350
500 HF
345
625
500/1
1.0
630
780 HF
538
910
1000/1
1.2
2x630
1400 HF
966
1900
1500/1
1.0
4x700
1700 HF
1380
3200
2000/1
1.0
4x900
2200 HF
1794
3450
3000/1
1.2
4x1400
COOLING SPECIFICATIONS
Type H Thyro-PX power controllers are self cooled, while type HF units are force
cooled. The fan in HF units require a separate power source at 230 V, 50/60 Hz.
Table 3‑9. Current derating
Air Temperature
I/I
RATED CURRENT
(A)
Self Cooling
Forced Cooling
-10°C to +25°C (14°F to 77°F)
1.10
1.10
30°C (86°F)
1.10
1.05
35°C (95°F)
1.10
1.00
40°C (104°F)
1.05
0.96
Advanced Energy
®
Thyro-PX® Power Controller
57010148-00B
Specifications
3‑9