2500 Series  

Fire Smoke Dampers 

Date 

Issue 

Spec. No. 

Page No. 

04/03/14  Rev 2  CE –FSD Sub 

PATENT APPLIED FOR 

General Description 

Construction Product Regulation 

To meet the requirements of the Construction 
Products Regulation 1st July 2013 Advanced Air fire 
dampers meet the requirements of the Product 
Standard BS EN 15650 with a classification under BS 
EN 13501-3 as stated in our Declaration Of 
Performance that has been assessed by the notified 
certification body BRE who have issued a Certificate 
of Consistency of Performance No:0832-CPR-P0005. 

The model 2550 is designed to prevent 
the spread of fire and smoke through 
ventilation ductwork in walls and floors. 
From receiving an alarm the power to 
the damper actuator is removed 
releasing the actuator spring to release 
closing the damper. The dampers also 
include electrical thermal sensor and a 
secondary mechanical fusible link that 
prevent the damper from opening if the 
temperature has reached 72

0

C. 

 
With the introduction of Construction 
Product Regulation on the 1st July 
2013 all fire dampers are required to 
meet the product standard BS EN 
15650. To achieve this standard the 
damper has to be tested to BS EN 
1366-2 dynamic fire test. The dampers 
are then classified to BS EN 13501-3 
that clearly states the integrity of the 
damper also in the way that damper 
was installed in the furnace. The 
standard also now included testing of 
fusible link to ISO 10294-4 that 
comprises of a dynamic release and 
holding tests. 
 
 

The maximum single section unit 

tested was 1000mm x 1000mm for both 
the HEVAC and AFS frame. The 
damper has been tested both ways 
round in both wall and floor 
installation's so there is no issue in co-
ordination caused by working out which 
side the fire will be on. 
The damper is supplied complete with 
actuator pre-wired into a junction box 
complete with test button reducing time 
and work on site. The dampers can be 
supplied with long spigots for installing 
access doors (optional) or short to 
reduce on space.  

Installation 

Damper/Model 

Classification 

Blockwork Wall 

2550- Motorised 

Fire Dampers 

E120 (ve i<—>o) s 

Drywall 

2550- Motorised 

Fire Dampers 

E120 (ve i<—>o) s 

Floor 

2550-Motorised 

Fire Damper 

E120 (ho i<—>o) s 

(P

ATENT

 P

ENDING

)

 

Summary of Contents for 2500 Series

Page 1: ...ble link that prevent the damper from opening if the temperature has reached 720 C With the introduction of Construction Product Regulation on the 1st July 2013 all fire dampers are required to meet t...

Page 2: ...ght to change any information without prior notice Burrell Way Thetford Norfolk IP24 3QU England Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers...

Page 3: ...Cambered grade 430 stainless steel Top Bottom Jambs Profiled grade 430 stainless steel riveted to damper frame Minimum Duct Size Rectangular 100mm x 100mm case size 250mm x 250mm Circular 100mm diamet...

Page 4: ...i o s TBC AFS Blockwork Wall BS EN 1366 2 120 min E120 ve i o s AFS Adjustable Frame System PATENT PENDING With the tighter requirements of the CPR and Building regulations with regard to CE labellin...

Page 5: ...ngland Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers Date Issue Spec No Page No 04 03 14 Rev 2 CE FSD Sub PATENT APPLIED FOR 5 Sizing Informati...

Page 6: ...using 750mm wide units tests performed in a clean system at suitable pressures and are P re ssu r e D r o p s F u l l y O p e n 1 1 0 1 0 0 1 0 0 0 1 1 0 1 0 0 V e lo c it y m s Pressure drop Pa 6 1 0...

Page 7: ...s aluminium alloy rivets or nylon bolts 9 All connecting ductwork must be independently supported within 1meter of the connections 10 An Access cover should be fitted on the appropriate side of the ba...

Page 8: ...y 7 The ductwork connecting to the dampers long spigot must overlap by 40mm The ductwork connecting to the short spigot must overlap the spigot by 40mm leaving 10mm clearance for any duct expansion in...

Page 9: ...tilation plant and ancillaries but should not exceed a maximum interval in excess of twelve months The report should be completed following the Maintenance Procedure included within this document Pre...

Page 10: ...ce checks can best be ascertained by system conditions or as directed by local regulations for ventilation plant and ancillaries but should not exceed a maximum interval in excess of twelve months The...

Page 11: ...ion of Fire Dampers must be done by competent trained persons who are familiar with the type of product They should follow the following essential safety practices Wear appropriate PPE gloves footwear...

Page 12: ...ght to change any information without prior notice Burrell Way Thetford Norfolk IP24 3QU England Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers...

Page 13: ...tch wiring for damage where applicable Check damper for cleanliness and clean where necessary Check the condition of the blades and seals rectify and report where necessary Confirm the safety closure...