Adp UHRS-030A Installation Instructions Manual Download Page 13

Page 13

 

6 - The unit may be vented vertically as a single appliance 

or in a common vent with other gas-fired appliances. 

In  common  venting  situations,  vent  connectors  for 

other appliances must maintain a 4” (102mm) vertical 

separation  between  the  vent  connectors.  Refer  to 

common  venting  tables  in  the  current  editions  of 

ANSI  Z223.1  or  CSA-B149  installation  compliance 

codes for proper vent size.

 

7 -  Clearance  to  combustible  material  is  6”  (152mm) 

for  single-wall  vent  material  except  where  a  listed 

clearance thimble is used. Clearance to combustible 

material for type B-1 vent or factory-built chimney is 

per manufacturer’s instructions.

 

8 - The vent connector shall be supported without any 

dips  or  sags.  Vertical  vents  shall  be  supported  in 

accordance  with  their  listing  and  manufacturers’ 

instructions. All horizontal vent connector runs shall 

have a slope up to the vertical vent of at least 1/4” 

per foot (1mm per 50mm).

 

9 - All vertical type B-1 vents, single-wall vertical vents 

(commercial  applications),  or  listed  chimney  lining 

systems must be terminated with a UL-listed (or other 

equivalent agency) vent cap or listed roof assembly.

 

10- The  vent  must  extend  at  least  3  feet  (1m)  above

the  highest  point  where  it  passes  through  a  roof

of a building. The vent must also extend at least 2

feet (1m) higher than any part of a building within a

horizontal distance of 10 feet (3m) unless otherwise

specified by ANSI Z223.1 or CSA-B149 installation

compliance codes. The vent must extend at least 5

feet  (2m)  above  the  highest  connected  equipment

flue collar

+25,=217$/9(17,1*

127(

&RPPRQYHQWLQJLVQRWDOORZHGZKHQKRUL]RQWDOO\

YHQWLQJWKHXQLWKHDWHU

127( 

 3UHFDXWLRQV PXVW EH WDNHQ WR SUHYHQW

GHJUDGDWLRQRIEXLOGLQJPDWHULDOVE\IOXHSURGXFWV

If the UH(RS,CM) unit heater is to be horizontally vented, 

a positive pressure may be created in the vent. The unit 

heater, when installed with horizontal venting, will perform 

as a category III appliance.

 

1 -  In  residential  applications  which  vent  horizontally, 

use  only  special  vent  materials  approved  for  use 

with Category III appliances.

 

2 -  The  vent  pipe  diameter  for  horizontal  installations 

shall  be  4”  (102mm)  diameter  on  30 ,  45 ,  60 , 

75 ,  090,  105 ,  125 ,  and  150   Btuh  units;  5” 

(127mm)  diameter  on  175 ,  200 ,  250 ,  &  300  

Btuh units; 6” (152mm) on 350 & 400  Btuh units. 

On 175-400 units, a flue transition piece (supplied) 

is required to fit over the outlet of the induced draft 

assembly on the appliance.

 

3 - The minimum horizontal vent length is 5 feet (2m).

 

4 - Refer to table 3 for maximum horizontal vent lengths.

 

5 -  If  possible,  do  not  terminate  the  horizontal  vent 

through  a  wall  that  is  exposed  to  prevailing  wind. 

Exposure  to  excessive  winds  can  affect  unit 

performance. If such a termination is necessary, use 

a  wind  block  to  protect  the  vent  termination  from 

direct winds.

 

6 -  Horizontal  vent  termination  must  be  free  from 

obstructions and at least 12” (305mm) above grade 

level and maximum snow height. 

7 - Do not install a horizontal vent termination directly 

below  roof  eaves  or  above  a  public    walkway,    or 

any other area where condensate dripping may be 

troublesome  and  may  cause  some  staining.  Avoid 

windows  where  steam  may  cause  fogging  or  ice 

buildup.

 

8 -  Minimum  clearance  for  horizontal  vent  termination 

from  any  door,  window,  non-mechanical  air  supply 

inlet is 4 feet below or to the side of opening; 1 foot 

above  opening  horizontally  for  United  States 

installations.  In  Canada,  minimum  clearance  for 

horizontal vent termination from any door, window, 

non-mechanical  air  supply  inlet  or  the  combustion 

air  inlet  to  any  other  appliance  is  12  inches  for 

appliances  10,000 to 100,000 Btuh, and 36 inches 

for appliance  100,000 Btuh. 

Refer to latest editions of the ANSI Z223.1 or CSA-B149 

for installation compliance codes and with local author- 

ities with jurisdiction.

 

9 - Vent terminal clearance to each side of a centerline 

extended  above  a  meter/regulator  assembly  and 

service regulator vent outlet must be in accordance 

with local installation codes and the requirements of 

the  gas  supplier  for  installations  in  the  United 

States. In Canada the clearance to  each side of a 

centerline 

extended 

above 

meter/regulator 

assembly and service regulator vent outlet must be 

3  feet(1m)  within  a  height  15  feet  above  the 

meter/regulator  assembly  and  3  feet  to  a  service 

regulator vent. 

10  -  Vent  termination  clearance  to  an  unvented  soffit 

or  within  2  feet  horizontally  of  a  ventilated  soffit 

must be in accordance with local installation codes 

and the requirements of the gas supplier. 

11  - When a vent termination is inside a corner formed 

by  two  exterior  walls  the  clearance  must  be  in 

accordance  with  local  installation  codes  and  the 

requirements of the gas supplier. 

12  -  Vent  termination  must  be  a  minimum  of  3 

feet(1m)  above  any  forced  air  inlet  (includes  fresh 

air  inlet  for  other  appliance,  such  as  a  dryer)  if 

within  10  feet  horizontally  for  United  States 

installations. In Canada, vent termination must have 

6 feet (2m) minimum clearance to a mechanical air-

supply  inlet  of  any  building.-  All  horizontal  vents 

which use special vent pipe for use with Category III 

appliances  must  terminate  with  an  approved 

Category III tee. Opening end must face downward. 

13  - When  termination  is  routed  through  combustible 

wall,  vent  termination  must  be  supported  using  a 

firestop  to  maintain  clearances  specified  on  unit 

rating plate. Inside edge of vent termination must be 

at least 16” (406mm) from outside wall. 

14  -  All  horizontal  vents  which  use  special  vent  pipe 

for use with Category III appliances must terminate 

with  an  approved  Category  III  tee.  Opening  end 

must face downward. 

15 For  horizontal  venting,  the  vent  pipe  shall  be 

supported  with  hangers  no more  than  3  feet.  (1m) 

Summary of Contents for UHRS-030A

Page 1: ...4 Su ersedes 3 3 1RWH 8QLW KHDWHUV DUH GHVLJQHG IRU LQGRRU XVH RQO 5 7 1 7 6 16758 7 216 25 8785 5 5 1 7 72 2 28 60 6 R QRW VWRUH RU XVH JDVROLQH RU RWKHU FLQLW RI WKLV RU DQ RWKHU DSSOLDQFH IRUPHG E D TXDOLILHG LQVWDOOHU VHUYLFH DJHQF RU WKH JDV VXSSOLHU R QRW WU WR OLJKW DQ DSSOLDQFH HDYH WKH EXLOGLQJ LPPHGLDWHO R QRW WRXFK DQ HOHFWULFDO VZLWFK GR QRW XVH DQ SKRQH LQ RXU EXLOGLQJ PPHGLDWHO FDOO ...

Page 2: ...ately if any shipping damage is found 6KLSSLQJ DQG 3DFNLQJ LVW UNIT HEATER BAG ASSEMBLY REMOVE BRAC ETS SECURING UNIT TO SHIPPING CRATE BEFORE INSTALLATION FLUE TRANSITION BURNER BOX HOOD UHCM 8QLWV Package 1 of 1 contains 1 Unit Heater 1 Burner box hood 1 5 Diameter Flue transition 6 diameter on 350 400 Bag assembly containing 1 Warranty card 1 Brand logo badge 8 10 16 X 5 8 SDST screws 2 Wire ti...

Page 3: ...723 9 7 1 5 5 2 MOUNTING SLOTS Typical 5 16 x 3 Inches 8 x 76 mm HANGING BRAC ETS 2 SERVICE ACCESS PANEL 6 9 ADJUSTABLE LOUVERS 1 25 8 56 0 16 216 QFKHV PP Model No A B C D in mm in mm in mm in mm UHRS 030A UHRS 045A 12 3 8 314 6 1 2 165 4 102 6 152 UHRS 060A UHRS 075A 17 1 2 445 6 1 4 159 6 1 8 156 3 5 8 92 UHRS 090A UHRS 105A 23 584 7 7 8 200 9 1 8 232 3 5 8 92 ...

Page 4: ...Page 4 ...

Page 5: ...LUE OUTLET 723 9 4 3 8 16 MOUNTING NUTS FOR UNIT SUSPENSION 16 406 1 2 13 5 3 8 137 1 2 13 31 7 8 810 10 5 8 270 35 1 4 895 10 1 2 267 2 1 2 64 3 1 8 79 8 0 0 16 216 QFKHV PP Model No A B C D in mm in mm in mm in mm UHCM 125 UHCM 150 19 1 2 495 18 1 2 470 12 1 4 311 4 3 4 121 UHCM 175 UHCM 200 25 635 23 3 4 603 9 1 2 241 3 76 ...

Page 6: ... 6 9 COMBUSTION AIR INDUCER DIRECT DRIVE FAN GAS VALVE HEAT EXCHANGER 16 406 1 2 13 31 7 8 810 10 5 8 270 5 3 8 137 10 1 2 267 1 2 13 35 1 4 895 3 76 2 5 8 67 3 1 8 79 8 0 0 16 216 QFKHV PP Model No A B C in mm in mm in mm UHCM 250 UHCM 300 37 5 8 956 36 1 2 927 15 7 8 403 UHCM 350 UHCM 400 47 1194 45 3 4 1162 20 1 2 521 ...

Page 7: ...Page 7 ...

Page 8: ...ation The installation must conform with local building codes or in the absence of local codes with the current edition of CSA B149 installation compliance codes All electrical wir ing and grounding for the unit must also comply with the current edition of CSA C22 1 Canadian Electrical Code These unit heaters are CSA certified for the installation clearances listed on the rating plate and in table...

Page 9: ...k Flue in mm in mm in mm in mm in mm 030 105 1 25 1 25 1 25 18 457 6 152 125 400 6 152 18 457 1 25 18 457 6 152 CAUTION Do not install unit heaters in close proximity to fire sprinklers Unit heater normal operating temperatures could result in fire sprinkler activation UHCM 125 400 UNITS Four mounting nuts are furnished Refer to dimension illustration Mounting nuts will accommodate 3 8 x 16 threaded...

Page 10: ... and release locking tab on the other end locking tab keeps the louver in place for shipping 2 If installing unit in a rotated position release locking tabs in the same manner as previous step Rotate each louver 180 and reinstall Remove and retain screws securing access panel Rotate access panel 180 and re secure using retained screws 3 Rotate louvers to direct airflow as desired 4 Choose location ...

Page 11: ...ion air inducer to the flue box See figure 3 4 Rotate the inducer 90 to the desired position Reinsert and tighten the inducer securing screws 5 The unit heater is now ready for installation as described in the Venting section FLUE BOX AND COMBUSTION AIR INDUCER ASSEMBLY 125 150 FLUE BOX FLUE BOX GASKET ORIFICE PLATE VEST PANEL ORIFICE PLATE GASKET COMBUSTION AIR INDUCER FIGURE 3 NOTE Local codes may...

Page 12: ...limitations listed in figure 3 Seal single wall vent material according to HQHUDO 5HFRPPHQGDWLRQV DQG 5HTXLUHPHQWV section 2 The vent connector shall be 4 102mm diameter on 30 45 60 75 090 105 125 and 150 Btuh units 5 127mm diameter on 175 200 250 300 Btuh units 6 152mm on 360 400 Btuh units On 175 400 units a flue transition piece supplied is required to fit over the outlet of the induced draft a...

Page 13: ...ect the vent termination from direct winds 6 Horizontal vent termination must be free from obstructions and at least 12 305mm above grade level and maximum snow height 7 Do not install a horizontal vent termination directly below roof eaves or above a public walkway or any other area where condensate dripping may be troublesome and may cause some staining Avoid windows where steam may cause foggin...

Page 14: ...revent combustion products from entering the structure If the unit is shut down for an extended period of time and will be exposed to sub freezing temperatures the condensate may freeze 18 Select a wall termination point that will maintain 1 4 rise per foot slope of horizontal run of vent pipe In areas where authorities having jurisdiction permit a downward slope of maximum 1 4 per foot is also ac...

Page 15: ...Page 15 ...

Page 16: ...burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe 6 After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous condition of use 7 If improper venting is observed during...

Page 17: ...anadian Electrical Code Part 1 NOTE Uninsulated ground wires must be wrapped in electrical tape to avoid damage to the electrical system 2 Make line voltage connections as shown in figure 8 On 030 105 units use pigtails provided in power entry box On 125 400 units connect wires to 2 pin P366 plug located on the A3 ignition control board For ease of installation disconnect P366 plug from J366 make ...

Page 18: ... L 1 W HT BL K BLK W HT BLU YEL COM P 001 GND Gr oundi ng Poi nt 4 GND BOARD GRN YEL BLK W HT GRN YEL W HT BL K P19 J 19 RE D 3 3 1 1 COM NO W HT W HT W HT 537992 02 0 0 537992 02 HI GH VOLTAGE POW ER CONNECTI ONS I GN CTRL A3 1 FACTORY I NSTALLED POW ER W I RI NG LOW VOLTAGE THERM OSTAT CONNECTI ONS HEAT W 1 3 9 24VAC I N P368 1 J 368 7 5 4 8 11 12 6 2 P364 P365 P363 L1 P367 J 367 1 3 5 6 R 24V C...

Page 19: ... RE D 4 CAI N 1 CAI L 1 W HT BL K BLK W HT BLU YEL COM P 001 GND Gr oundi ng Poi nt 4 GND BOARD GRN YEL BLK W HT GRN YEL W HT W HT GRY W HT 538025 02 1 0 538025 02 HI GH VOLTAGE POW ER CONNECTI ONS I GN CTRL A3 1 LOW VOLTAGE THERM OSTAT CONNECTI ONS HEAT W 1 3 9 24VAC I N P368 1 J 368 7 5 4 8 11 12 6 2 P364 P365 P363 L1 P367 J 367 1 3 5 6 R 24V COM M ON C 24V POW ER R BLOW ER G G C P366 W 2 W 1 N ...

Page 20: ...M R L1 HI 2 1 R C N W HT RE D 4 CAI N 1 CAI L 1 W HT BL K BLK W HT BLU YEL COM P 001 GND Gr oundi ng Poi nt 4 GND BOARD GRN YEL BLK W HT GRN YEL W HT W HT W HT GRY W HT BRN 538024 02 1 0 538024 02 I GN CTRL A3 1 FI ELD PROVI DED POW ER W I RI NG CONNECT TO P366 AND GREEN GROUND SCREW LOCATED I NSI DE UNI T LOW VOLTAGE THERM OSTAT CONNECTI ONS HEAT W 2 HEAT W 1 3 9 24VAC I N P368 1 J 368 7 5 4 8 11...

Page 21: ...at a manual main shutoff valve and union furnished by installer be installed external to the unit Union must be of the ground joint type A drip leg should be readily accessible to per mit cleaning and emptying See figure 10 NOTE If a switch box is mounted over electrical knock outs on back of unit leave a minimum of 4 102mm clearance between switch box and drip leg A 1 8 NPT plugged tap shall be ins...

Page 22: ... the building there may be smoke on start up WARNING Danger of explosion Can cause injury or product or property damage You must follow these instructions exactly BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor Use only your hand to move the switch Never use tools If the switch will not m...

Page 23: ... the burner heads flashback or burning within the burner The flames should be predominantly blue in color and should be approximately centered in the tubes with no apparent impingement taking place 7 Theignitioncontrolwillenergizethefanapproximately 30 seconds after ignition is established 8 After the thermostat demand is satisfied the gas valve is closed Thirty seconds after the demand is satisfied t...

Page 24: ...the jurisdiction of local authorities ADP recommends derating 4 1000 feet above 4 500 feet Refer to table 6 for natural gas manifold pressures and the Engineering Handbook for high altitude kit part numbers Units may be fired at full input up to 2000 feet 610m above sea level Above 2000 feet 610m manifold pressure must be adjusted Adjust pressure regulator to pressure shown in table 5 In the US un...

Page 25: ...cleaned prior to each heating season The sequence of operation should be as follows 1 7XUQ Rႇ ERWK HOHFWULFDO DQG JDV VXSSO WR XQLW 2 Disconnect combustion air inducer wiring 3 Remove combustion air inducer assembly Remove ÀXH ER I QHFHVVDU UHPRYH LQGXFHU DVVHPEO IURP ÀXH ER OHDQ ÀXH ER ZLWK ZLUH EUXVK 4 Remove burners as described in Burners section 5 Clean tubes with a wire brush 5HDVVHPEOH XQLW...

Page 26: ... thermostat call for heat and follow the operating instructions under Unit Start Up and Operation REPAIR PARTS When ordering repair parts include the complete unit model number listed on the unit rating plate For example UHRS 45A 1 Contact the installing dealer or visit www adpnow com for a list of dealers in the area Include manufacturer s or distributor s name and address It is a requirement in ...

Page 27: ...83 8 standard Electrical Connections Tight 67 57 83 1 3 5 250 1 67 Job No City City Serial No Date State Province Service Technician Air Shutters Properly Adjusted If Installed Flue Connections Tight 7 50267 7 Calibrated Heat Anticipator Properly Set Level Manifold Pressure Blower Motor Amps Blower Motor Lubrication O Gas Piping Connections Tight Leak Tested State Province Fan Timer Operation Chec...

Page 28: ...VHQWV WKH WRWDO ZDUUDQW SHULRG IRU WKH VSHFLILF FRPSRQHQW 3 DW LWV RSWLRQ ZLOO IXUQLVK D UHSODFHPHQW KHDW H FKDQJHU RU DOORZ D FUHGLW LQ WKH DPRXQW RI WKH KHDW H FKDQJHU RULJLQDO VHOOLQJ SULFH WRZDUG WKH SXUFKDVH RI D QHZ 3 XQLW KHDWHU RU LQIRUPDWLRQ RQ WKLV SURGXFWV ZDUUDQW LQFOXGLQJ FRPSOHWH ZDUUDQW WHUPV UHJLVWHULQJ IRU DQ H WHQGHG ZDUUDQW RU LQVWUXFWLRQV RQ KRZ WR ILOH D ZDUUDQW FODLP SOHDVH J...

Reviews: