6.5 Fan Tray Connector Pin Assignment 

Table 6: Fan Tray Connector Pin Assignment 

Pin#

 

Signal

 

Description

 

Pin#

 

Signal

 

Description

 

A1 

-48V_B 

-48VDC Feed B 

E1 

-48V_A 

-48VDC Feed A 

A2 

-48V_B 

-48VDC Feed B 

E2 

-48V_A 

-48VDC Feed A 

A3 

-48V_B 

-48VDC Feed B 

E3 

 

 

A4 

 

 

E4 

 

 

A5 

SCL_A 

IPMB A Clock 

E5 

I2C_SCL_B 

I2C B Clock 

A6 

SDA_A 

IPMB A Data 

E6 

I2C_SDA_B 

I2C B Data 

A7 

SCL_B 

IPMB B Clock 

E7 

GND 

Fan Tray Presence, connected to GND 

A8 

 

 

E8 

 

 

A9 

VRTN_B 

RTN Feed B 

E9 

 

 

A10 

VRTN_B 

RTN Feed B 

E10 

VRTN_A 

RTN Feed A 

A11 

VRTN_B 

RTN Feed B 

E11 

VRTN_A 

RTN Feed A 

B1 

-48V_B 

-48VDC Feed B 

F1 

-48V_A 

-48VDC Feed A 

B2 

-48V_B 

-48VDC Feed B 

F2 

-48V_A 

-48VDC Feed A 

B3 

-48V_B 

-48VDC Feed B 

F3 

 

 

B4 

 

 

F4 

 

 

B5 

I2C_B CONTROL 

I2C B Line Busy Signal 

F5 

GND 

Logic Ground 

B6 

SDA_B 

IPMB B Data 

F6 

INT_I2C_A 

Interrupt Signal of I2C A Line 

B7 

INT_I2C_B 

Interrupt Signal of I2C B Line 

F7 

GND 

Logic Ground 

B8 

 

 

F8 

INT_ERROR 

Check Error Signal 

B9 

VRTN_B 

RTN Feed B 

F9 

 

 

B10 

VRTN_B 

RTN Feed B 

F10 

VRTN_A 

RTN Feed A 

B11 

VRTN_B 

RTN Feed B 

F11 

VRTN_A 

RTN Feed A 

C1 

-48V_B 

-48VDC Feed B 

G1 

-48V_A 

-48VDC Feed A 

C2 

-48V_B 

-48VDC Feed B 

G2 

-48V_A 

-48VDC Feed A 

C3 

 

 

G3 

 

 

C4 

 

 

G4 

SAP_PRESENT 

Presence Signal of SAP 

C5  PEM_PRESNET_L 

Presence Signal of Left PEM 

G5 

I2C_SCL_A 

I2C A Clock 

C6 

H2 

 

G6 

I2C_SDA_A 

I2C A Data 

C7 

ERROR 

Error Signal 

G7  SHELF_PRESENT 

Presence Signal of Shelf Manager 

C8 

 

 

G8 

Monitor 

Monitor Signal 

C9 

 

 

G9 

 

 

C10 

VRTN_B 

RTN Feed B 

G10 

VRTN_A 

RTN Feed A 

C11 

VRTN_B 

RTN Feed B 

G11 

VRTN_A 

RTN Feed A 

D1 

 

 

H1 

-48V_A 

-48VDC Feed A 

D2 

 

 

H2 

-48V_A 

-48VDC Feed A 

D3 

 

 

H3 

 

 

D4 

 

 

H4 

INT_PCA9555_R 

Interrupt Signal of Right PEM PCA9555 

D5 

INT_PCA9555_L 

Interrupt Signal of Left PEM PCA9555 

H5 

+3.6V 

 

D6  PEM_PRESNET_R 

Presence Signal of Right PEM 

H6 

I2C_A CONTROL 

I2C A Line Busy Signal 

D7 

FAN_PRESENT 

Presence Signal of Fan Tray 

H7 

INT_Monitor 

Check Monitor Signal 

D8 

 

 

H8  FILTER_PRESENT 

Presence Signal of Filter 

D9 

 

 

H9 

 

 

D10 

 

 

H10 

VRTN_A 

RTN Feed A 

D11 

 

 

H11 

VRTN_A 

RTN Feed A 

 

 

Summary of Contents for aTCA-80606PA

Page 1: ...aTCA 80606PA 6U 6 Slot AC Powered AdvancedTCA Shelf User s Manual Manual Rev 1 0 Revision Date December 20 2018 Part No 50 1G047 1000...

Page 2: ...triction of Hazardous Substances RoHS directive and Waste Electrical and Electronic Equipment WEEE directive Environmental protection is a top priority for ADLINK We have enforced measures to ensure t...

Page 3: ...Channel Interface 10 3 6 Intelligent Platform Management Bus IPMB 11 3 7 Shelf SEEPROM 11 3 8 Logic Ground 12 4 Air Filter 13 4 1 Introduction 13 5 Shelf Ground Connection 14 5 1 Specification for th...

Page 4: ...rd Air Distribution 24 8 2 2 Rear Board Air Distribution 25 9 Shelf Management 26 9 1 Shelf Managers 26 9 2 Introduction 27 9 3 Front Panel Components 28 9 4 Hardware Address 28 10 Technical Data 29 1...

Page 5: ...ages over 60 VDC can be present in this equipment As defined in the PICMG 3 0 Specification this equipment is intended to be accessed to be installed and maintained by qualified and trained service pe...

Page 6: ...d providing the connectors for the front boards Power distribution management and auxiliary signal connections are supported CDM Chassis Data Module Chassis Enclosure containing subrack backplane boar...

Page 7: ...Two Push Pull Fan Tray arrangement provides optimized cooling for ATCA blades with fault tolerant capability front pluggable hot swappable with 6 high speed fans per tray Two dedicated Shelf Manager...

Page 8: ...8 aTCA 80606PA Figure 2 Rear View 8 Power input 2 10 ESD Wrist Strap 9 Shelf Ground Terminal 11 Power input 1...

Page 9: ...t HW Address Hex IPMB Address Hex Update Channel Routing Node 6 6 46 8C Node 5 5 45 8A Node 4 4 44 88 Node 3 3 43 86 Hub Slot 2 2 42 84 Hub Slot 1 1 41 82 3 2 Base Interface Logical slots 1 and 2 are...

Page 10: ...ate Channels are wired between two redundant ATCA Backplane slots as 10 differential pairs with 100 Ohms impedance see Table 2 The Update Channel is intended to pass information between two redundant...

Page 11: ...ROM contains as example A list of which slots are connected together How the update channels are routed How many slots are in the system What the maximum power is to each slot The serial number of the...

Page 12: ...gic Ground and Shelf Ground To connect Logic Ground and Shelf Ground the mounting screws at the positions marked by arrow must be fixed Figure 4 Logic Ground By default Logic Ground and Shelf Ground a...

Page 13: ...lter The filter element is an open cell polyurethane foam special coating to provide improved fire retardation and fungi resistance The filter meets the requirements of the Telcordia Technologies Gene...

Page 14: ...nd terminal provides two threads M5 with a 16 0mm spacing between thread centers to connect a two hole lug Shelf ground terminal cable Figure 4 Shelf Ground Terminal Please note that in a typical tele...

Page 15: ...IPM controller is located on the Fan Tray and has 2 operation modes 6 2 1 Shelf Manager Mode As soon as a Shelf Manager is plugged in and becomes active the IPM controller switches automatically into...

Page 16: ...u can select either the exhaust temperature from the left Fan Tray or the fixed fan speed as reference to control the fan speed By default the fixed speed of 50 full speed is used to determine the fan...

Page 17: ...t is provided so that service personnel can be trained to look for a blue LED to be illuminated on any active component before removing it from the system Once the operator pushes the Hot Swap button...

Page 18: ...ic Ground B8 F8 INT_ERROR Check Error Signal B9 VRTN_B RTN Feed B F9 B10 VRTN_B RTN Feed B F10 VRTN_A RTN Feed A B11 VRTN_B RTN Feed B F11 VRTN_A RTN Feed A C1 48V_B 48VDC Feed B G1 48V_A 48VDC Feed A...

Page 19: ...19 aTCA 80606PA 6 6 Fan Tray IPMB Addresses Geographic address pins H2 at the Fan Tray Backplane connector determine the hardware addresses of the devices Table 7 Fan Tray IPMB address...

Page 20: ...1 1 configuration The Output voltage of the PSUs is 53 5V DC Because the nominal supply voltage for ATCA systems acc to the PICMG specification is 48V DC all signal names in this Manual with exception...

Page 21: ...21 aTCA 80606PA 7 2 Power Distribution Figure 7 Power Distribution...

Page 22: ...t CAN bus communication Table 8 Basic Specifications for the PSUs 230 V Operation Input Voltage nominal 230 VAC Input Voltage Range max 176V AC 290V AC Input Frequency Range 45 Hz 66 Hz Output Voltage...

Page 23: ...agers and the Fan Trays The Power is divided in 2 output branches towards the backplane If the joint power capability of all ATCA boards assigned to a branch is greater than the calculated branch powe...

Page 24: ...fan failure Figure 10 General airflow path for the 6U 6 slot ATCA Shelf 8 2 Cooling Capacity The maximum system airflow all fans at full speed is 387 3 CFM The maximum air distribution is measured wi...

Page 25: ...25 aTCA 80606PA 8 2 2 Rear Board Air Distribution The airflow is measured with impedance boards acc to the PICMG 3 0 R3 0 specification Rear board pressure drop 24 Pa at 0 14 m min...

Page 26: ...ent the I C components of the PEMs and the SEEPROM are connected to the internal I C bus on the Fan Trays The on blade Shelf Manager has access to these components via the IPM controller of the Fan Tr...

Page 27: ...ch is typically implemented over Ethernet The Shelf management based on the Pigeon Point Shelf management solution for AdvancedTCA products The Shelf management software executes on the pigeon point S...

Page 28: ...are Address The Shelf Manager reads the hardware address and parity bit from the backplane connector of the Dedicated Shelf Manager slot Geographic address pins HA0 HA7 at the Backplane connector dete...

Page 29: ...C 230 VAC Input voltage range 85 175 VAC 176 290 VAC Input Power Protection 17 A Power and Cooling Capacity Front Boards 300 W board RTM 35 W board Environmental Ambient temperature 5 C 40 C long term...