aTCA-80606PA 

6.3 Fan Tray Signals 

The Fan Tray provides signals for: 

  Fuse monitoring 

  Status of the Hot Swap Controller 

  Fan Speed 

  Temperature 

These signals are controlled by the IPM Controller devices on the Fan Tray PCB. The Shelf 
Manager has access to these signals via IPMB. 

 

6.4 Fan Tray Indicators 

The front panel includes a green Fan Tray OK LED, a red Fan Tray Fault LED, and a blue 
Hot Swap LED.  

The Hot Swap push button indicates to the Shelf Managers that the Fan Tray is about to 
be removed. Its use is optional, but it is provided so that service personnel can be trained 
to look for a blue LED to be illuminated on any active component before removing it from 
the system. Once the operator pushes the Hot Swap button, the Shelf Manager is 
informed of the pending extraction. When the Shelf Manager feels it is “safe“ to remove 
the Fan Tray, the blue Hot Swap LED illuminates solid. 

 

Table 5: LEDs on Fan Tray front panel 

Color

 

Description

 

Status

 

Condition

 

Green 

Fan Tray OK LED 

Off 

No Power to the Fan Tray 

Solid green 

Normal Operation 

Red 

Fan Tray Fault LED 

Solid red 

Attention Status (error condition) 

Blue 

Hot Swap LED 

Off 

No Power to the Fan Tray, or  
not OK to extract the Fan Tray 

Short blink 

Preparing for extraction 

Solid blue 

Ready to remove 

 
 

 

Summary of Contents for aTCA-80606PA

Page 1: ...aTCA 80606PA 6U 6 Slot AC Powered AdvancedTCA Shelf User s Manual Manual Rev 1 0 Revision Date December 20 2018 Part No 50 1G047 1000...

Page 2: ...triction of Hazardous Substances RoHS directive and Waste Electrical and Electronic Equipment WEEE directive Environmental protection is a top priority for ADLINK We have enforced measures to ensure t...

Page 3: ...Channel Interface 10 3 6 Intelligent Platform Management Bus IPMB 11 3 7 Shelf SEEPROM 11 3 8 Logic Ground 12 4 Air Filter 13 4 1 Introduction 13 5 Shelf Ground Connection 14 5 1 Specification for th...

Page 4: ...rd Air Distribution 24 8 2 2 Rear Board Air Distribution 25 9 Shelf Management 26 9 1 Shelf Managers 26 9 2 Introduction 27 9 3 Front Panel Components 28 9 4 Hardware Address 28 10 Technical Data 29 1...

Page 5: ...ages over 60 VDC can be present in this equipment As defined in the PICMG 3 0 Specification this equipment is intended to be accessed to be installed and maintained by qualified and trained service pe...

Page 6: ...d providing the connectors for the front boards Power distribution management and auxiliary signal connections are supported CDM Chassis Data Module Chassis Enclosure containing subrack backplane boar...

Page 7: ...Two Push Pull Fan Tray arrangement provides optimized cooling for ATCA blades with fault tolerant capability front pluggable hot swappable with 6 high speed fans per tray Two dedicated Shelf Manager...

Page 8: ...8 aTCA 80606PA Figure 2 Rear View 8 Power input 2 10 ESD Wrist Strap 9 Shelf Ground Terminal 11 Power input 1...

Page 9: ...t HW Address Hex IPMB Address Hex Update Channel Routing Node 6 6 46 8C Node 5 5 45 8A Node 4 4 44 88 Node 3 3 43 86 Hub Slot 2 2 42 84 Hub Slot 1 1 41 82 3 2 Base Interface Logical slots 1 and 2 are...

Page 10: ...ate Channels are wired between two redundant ATCA Backplane slots as 10 differential pairs with 100 Ohms impedance see Table 2 The Update Channel is intended to pass information between two redundant...

Page 11: ...ROM contains as example A list of which slots are connected together How the update channels are routed How many slots are in the system What the maximum power is to each slot The serial number of the...

Page 12: ...gic Ground and Shelf Ground To connect Logic Ground and Shelf Ground the mounting screws at the positions marked by arrow must be fixed Figure 4 Logic Ground By default Logic Ground and Shelf Ground a...

Page 13: ...lter The filter element is an open cell polyurethane foam special coating to provide improved fire retardation and fungi resistance The filter meets the requirements of the Telcordia Technologies Gene...

Page 14: ...nd terminal provides two threads M5 with a 16 0mm spacing between thread centers to connect a two hole lug Shelf ground terminal cable Figure 4 Shelf Ground Terminal Please note that in a typical tele...

Page 15: ...IPM controller is located on the Fan Tray and has 2 operation modes 6 2 1 Shelf Manager Mode As soon as a Shelf Manager is plugged in and becomes active the IPM controller switches automatically into...

Page 16: ...u can select either the exhaust temperature from the left Fan Tray or the fixed fan speed as reference to control the fan speed By default the fixed speed of 50 full speed is used to determine the fan...

Page 17: ...t is provided so that service personnel can be trained to look for a blue LED to be illuminated on any active component before removing it from the system Once the operator pushes the Hot Swap button...

Page 18: ...ic Ground B8 F8 INT_ERROR Check Error Signal B9 VRTN_B RTN Feed B F9 B10 VRTN_B RTN Feed B F10 VRTN_A RTN Feed A B11 VRTN_B RTN Feed B F11 VRTN_A RTN Feed A C1 48V_B 48VDC Feed B G1 48V_A 48VDC Feed A...

Page 19: ...19 aTCA 80606PA 6 6 Fan Tray IPMB Addresses Geographic address pins H2 at the Fan Tray Backplane connector determine the hardware addresses of the devices Table 7 Fan Tray IPMB address...

Page 20: ...1 1 configuration The Output voltage of the PSUs is 53 5V DC Because the nominal supply voltage for ATCA systems acc to the PICMG specification is 48V DC all signal names in this Manual with exception...

Page 21: ...21 aTCA 80606PA 7 2 Power Distribution Figure 7 Power Distribution...

Page 22: ...t CAN bus communication Table 8 Basic Specifications for the PSUs 230 V Operation Input Voltage nominal 230 VAC Input Voltage Range max 176V AC 290V AC Input Frequency Range 45 Hz 66 Hz Output Voltage...

Page 23: ...agers and the Fan Trays The Power is divided in 2 output branches towards the backplane If the joint power capability of all ATCA boards assigned to a branch is greater than the calculated branch powe...

Page 24: ...fan failure Figure 10 General airflow path for the 6U 6 slot ATCA Shelf 8 2 Cooling Capacity The maximum system airflow all fans at full speed is 387 3 CFM The maximum air distribution is measured wi...

Page 25: ...25 aTCA 80606PA 8 2 2 Rear Board Air Distribution The airflow is measured with impedance boards acc to the PICMG 3 0 R3 0 specification Rear board pressure drop 24 Pa at 0 14 m min...

Page 26: ...ent the I C components of the PEMs and the SEEPROM are connected to the internal I C bus on the Fan Trays The on blade Shelf Manager has access to these components via the IPM controller of the Fan Tr...

Page 27: ...ch is typically implemented over Ethernet The Shelf management based on the Pigeon Point Shelf management solution for AdvancedTCA products The Shelf management software executes on the pigeon point S...

Page 28: ...are Address The Shelf Manager reads the hardware address and parity bit from the backplane connector of the Dedicated Shelf Manager slot Geographic address pins HA0 HA7 at the Backplane connector dete...

Page 29: ...C 230 VAC Input voltage range 85 175 VAC 176 290 VAC Input Power Protection 17 A Power and Cooling Capacity Front Boards 300 W board RTM 35 W board Environmental Ambient temperature 5 C 40 C long term...

Page 30: ...30 aTCA 80606PA 10 1 Shelf Mechanical Dimensions All dimensions below are in mm Figure 14 Front View Dimensions Figure 15 Side View Dimensions...

Page 31: ...200 Toll Free 1 800 966 5200 USA only Fax 1 408 360 0222 Email info adlinktech com ADLINK Technology China Co Ltd Address 300 Fang Chun Rd Zhangjiang Hi Tech Park Pudong New Area Shanghai 201203 China...

Reviews: