background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com S.r.l. 

 

User Manual   

EtherCAT Master / CANopen

 

 

Document code: MN67E58_ENG     Revision 1.000   Page 24 of 31

 

 

 
SET PDO ACCESS:

 
By pressing the “

Set PDO Access

” button from the main window for SW67E58 (Fig. 2) the window “Set PDO Access” appears (Fig. 7a and 

7b). 

 

This window is made to create the Receive and the Transmit PDO in the CANopen side, and to indicate which bytes are associated to these 
PDO. 
It is divided in two parts, the " Receive PDO" and the " Transmit PDO ". The first part is used to receive PDO in the CANopen network and 
copy the data in the EtherCAT

 

array. The second part is used to transmit PDO in the CANopen network with the data of EtherCAT

 

array. 

 

The data of the columns in the “Receive PDO” have the 
following meanings: 

 

In the Field "

Cob-ID

" the address for the PDO is 

defined; 

 

In  the  Field  "

Dimension

"  the  dimension  of  the 

PDO is defined  (it can be between 1 and 8); 

 

In  the  Field  "

Add  B1

"  the  first  byte  where  the 

data  will  be  saved  in  the  EtherCAT  array  is 
defined; 

 

In the Field "

Add B2

" the second byte where the 

data  will  be  saved  in  the  EtherCAT  array  is 
defined (only if 

Dimension 

> 1); 

 

In  the  Field  "

Add  B3

"  the  third  byte  where  the 

data  will  be  saved  in  the  EtherCAT  array  is 
defined (only if 

Dimension 

> 2); 

 

In the Field "

Add B4

" the fourth byte where the data will be saved in the EtherCAT array is defined (only if 

Dimension 

> 3); 

 

In the Field "

Add B5

" the fifth byte where the data will be saved in the EtherCAT array is defined (only if 

Dimension 

> 4); 

 

In the Field "

Add B6

" the sixth byte where the data will be saved in the EtherCAT array is defined (only if 

Dimension 

> 5); 

 

In the Field "

Add B7

" the seventh byte where the data will be saved in the EtherCAT array is defined (only if 

Dimension 

> 6); 

 

In the Field "

Add B8

" the eighth byte where the data will be saved in the EtherCAT array is defined (only if 

Dimension 

> 7); 

 

The  field  “

TimeOut

”  is  used  for  put  at  zero  the  data  into  EtherCAT  if  the  PDO  doesn’t  arrive  with  a  frequency  less  than  the  time 

expressed  in  the  field.  If  the  value  in  the  field  is  0,  it  means  that  you  don’t  want  to  use  this  feature,  and  so  the  value  is  never 
deleted; 

 

In the field "

Mnemonic

" the description for the PDO is defined.   

Figure 7a: “Set PDO Access – Receive PDO” window

 

Summary of Contents for HD67E58-A1

Page 1: ...e www adfweb com Product HD67E55 BACnet Master www adfweb com Product HD67E56 BACnet Slave www adfweb com Product HD67E57 CAN www adfweb com Product HD67E59 DeviceNet Master www adfweb com Product HD6...

Page 2: ...DARDS 30 WARRANTIES AND TECHNICAL SUPPORT 31 RETURN POLICY 31 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document i...

Page 3: ...evice can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation...

Page 4: ...Industrial Electronic Devices ADFweb com S r l User Manual EtherCAT Master CANopen Document code MN67E58_ENG Revision 1 000 Page 4 of 31 EXAMPLE OF CONNECTION...

Page 5: ...Industrial Electronic Devices ADFweb com S r l User Manual EtherCAT Master CANopen Document code MN67E58_ENG Revision 1 000 Page 5 of 31 CONNECTION SCHEME Figure 1 Connection scheme for HD67E58 A1...

Page 6: ...formation between EtherCAT bus and CANopen bus Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V DC Wide temperature range 40 C 85 C 40 F 185 F CONFIGURATION You need Composi...

Page 7: ...E58_ENG Revision 1 000 Page 7 of 31 POWER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 8V 24V 12V 35V Consumption a...

Page 8: ...the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 of Dip Switch A at ON position is used f...

Page 9: ...n Blinks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 EtherCAT comm green It blinks when EtherCAT communication is running Blinks quickly Boot state Blinks very s...

Page 10: ...y node The EtherCAT slave devices read the data addressed to them while the telegram passes through the device processing data on the fly In other words real time data and messages are prioritized ove...

Page 11: ...OPEN For terminating the CAN line with a 120 resistor it is necessary that the Dip1 of Dip Switch C is at ON position Cable characteristics DC parameter Impedance 70 Ohm m AC parameters Impedance 120...

Page 12: ...uns with Windows called SW67E58 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present on o...

Page 13: ...iguration A device s configuration can also be imported or exported To clone the configurations of a programmable EtherCAT Master CANopen Converter in order to configure another device in the same man...

Page 14: ...the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible t...

Page 15: ...erCAT Master CANopen Document code MN67E58_ENG Revision 1 000 Page 15 of 31 In the section Software Settings it is possible to enable disable some keyboard s commands for an easier navigation inside t...

Page 16: ...er is defined In the field Secondary DNS the IP Address of the secondary DNS server is defined The means for the fields for the CANopen are In the field Device ID the ID of the CANopen side is defined...

Page 17: ...ernet section are In the fields IP ADDRESS the IP address of Ethernet side of the converter is defined In the fields SUBNET Mask the SubNet Mask of Ethernet side of the converter is defined In the fie...

Page 18: ...lave devices to connect and the parameters to read write Below the EtherCAT Master Devices List the list of the EtherCAT devices to connect is defined It is possible to import the slaves using the sta...

Page 19: ...file PROCESS DATA The means of the fields are In the field Slot the selected Slot is defined In the field Name the name of the variable is defined In the field Type the format of the EtherCAT variable...

Page 20: ...e memory array where the read value of the variable is mapped is defined In the field Start Bit R the starting bit of the selected Position where the variable is mapped is defined In the field Time Re...

Page 21: ...data of the columns have the following meanings In the field Index the address of the SDO is defined In the field SubIndex the second address of the SDO is defined If the field N Byte the dimension o...

Page 22: ...In the field Device ID insert the ID of the device to read In the field Index the address for the SDO is defined In the field SubIndex the second address for the SDO is defined In the field N Byte the...

Page 23: ...On Change is checked the gateway sends the Write SDO request when the data change the value In the field Address Byte1 the address of the EtherCAT array where reading the first byte of the SDO write i...

Page 24: ...he Field Add B2 the second byte where the data will be saved in the EtherCAT array is defined only if Dimension 1 In the Field Add B3 the third byte where the data will be saved in the EtherCAT array...

Page 25: ...array is defined only if Dimension 3 In the Field Add B5 the fifth byte where the data will be loaded in the EtherCAT array is defined only if Dimension 4 In the Field Add B6 the sixth byte where the...

Page 26: ...rnet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip1 o...

Page 27: ...gram inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 10 or 11 make sure that you have the administrator privileges In case you have to program m...

Page 28: ...ial Electronic Devices ADFweb com S r l User Manual EtherCAT Master CANopen Document code MN67E58_ENG Revision 1 000 Page 28 of 31 MECHANICAL DIMENSIONS Figure 10 Mechanical dimensions scheme for HD67...

Page 29: ...d combination of the following HD67E58 xx Connectors Type 1 Removable 5mm Screw Terminal Enclosure Type A 1M 35mm DIN Rail mounting Device Family HD67E58 EtherCAT Master CANopen Converter Order Code H...

Page 30: ...ion systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recy...

Page 31: ...do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to...

Reviews: