SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, EtherCAT and
BACnet.
By Pressing the “
Set Communication
” button from the main window for SW67E05 (Fig. 2)
the window “Set Communication” appears (Fig. 3).
The means of the fields for “EtherCAT Slave” are:
In the field “
Revision Number
” the revision number of the converter is defined;
In the field “
Slave Name
” the name of the converter is defined;
In the field
“Node Address
” the ID of the converter is defined.
In the section “BACnet Master” it is possible to select the type of BACnet to use from:
BACnet/IP (it uses Ethernet);
BACnet MS/TP (it uses RS485).
If selected “BACnet/IP” the means of the fields for “BACnet” are:
In the fields “
IP ADDRESS
” the IP address of BACnet/IP side of the converter is
defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of BACnet/IP side of the converter is
defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This feature
can be enabled or disabled pressing the Check Box field. This feature is used for going
out of the net;
In the field “
Port
” the port used for BACnet communication is defined. The default port
used for BACnet communication is 47808, but is possible to insert any value;
In the field "
BACnet Device Name
" the name of BACnet/IP side of the converter is
defined;
In the field “
Device Identifier
” the device instance of BACnet/IP side of the converter
is defined;
In the field “
TimeOut Polling (ms)
” the timeout for the BACnet requests is defined.
Figure 3a: “Set Communication” window