SCENE CONTROL
Modbus register
Type
Description
64
Holding register
Byte 1 (most significant):
Control byte: it must be increased of +1 every times
that the command must be sent on DALI.
Byte 0 (least significant):
ID of DALI device to command (for commands, most
significant bit must be set to ‘1’ as DALI specifications):
0-63 = Single DALI device
64-79 = Groups
127 = Broadcast
65
Holding register
Byte 1 (most significant):
Scene to control:
0x10 = Scene 0
0x11 = Scene 1
0x12 = Scene 2
0x13 = Scene 3
0x14 = Scene 4
0x15 = Scene 5
0x16 = Scene 6
0x17 = Scene 7
0x18 = Scene 8
0x19 = Scene 9
0x1A = Scene 10
0x1B = Scene 11
0x1C = Scene 12
0x1D = Scene 13
0x1E = Scene 14
0x1F = Scene 15
Note:
All the registers can be read back using Modbus function 03 in order to see the last commands sent.