Setting new Fade Rate value
This command is used to program the new Fade Rate value in the DALI devices.
REQUEST
S_RAT_
id
_
val
(ASCII format)
Where:
‘id’ = ID of the DALI node (0 ÷ 63) or group (64 ÷ 79) or broadcast (80).
‘val’ = value of new Fade Rate value to set (0 ÷ FF, Hex representation)
Note:
Just ‘id’ and ‘val’ are variables, the rest of the ASCII string is fixed.
Setting new Fade Time value
This command is used to program the new Fade Time value in the DALI devices.
REQUEST
S_TIM_
id
_
val
(ASCII format)
Where:
‘id’ = ID of the DALI node (0 ÷ 63) or group (64 ÷ 79) or broadcast (80).
‘val’ = value of new Fade Time value to set (0 ÷ FF, Hex representation)
Note: