Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
DALI / Ethernet
Document code: MN67839_ENG Revision 1.001 Pagina 45 di 62
Scene Programming
This commands are used to program the scenes inside the DALI nodes. It is necessary to send two consecutive commands for the
programming.
REQUEST 1
Byte Number
Description
1
0x00
2
0x10
3
0x00
4
0x00
5
0x00
6
0x02
7
0x04
8
Counter (increased for every command) (Hex)
9
0xD1
10
ADV (Hex)
11
0x00
REQUEST 2
Byte Number
Description
1
0x00
2
0x10
3
0x00
4
0x00
5
0x00
6
0x02
7
0x04
8
Counter (increased for every command) (Hex)
9
DALI ID + 0x80 (Hex)
10
Scene 0x40 (Hex)
11
0x00