LEDS:
The device has got five LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
LED
Normal Mode
Boot Mode
1: Device State (green)
Blinks slowly (~1Hz)
Blinks quickly:
Boot state
Blinks very slowly (~0.5Hz):
update in progress
2: EtherNet/IP
communication (yellow)
Blinks when EtherNet/IP communication is running
Blinks quickly:
Boot state
Blinks very slowly (~0.5Hz):
update in progress
3: KNX communication
(yellow)
Blinks when KNX communication is running
Blinks quickly:
Boot state
Blinks very slowly (~0.5Hz):
update in progress
4: Not used (yellow)
OFF
Blinks quickly:
Boot state
Blinks very slowly (~0.5Hz):
update in progress
5: KNX prog. (red)
ON:
KNX program mode activated
OFF:
KNX program mode not activated
OFF