Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
EtherNet/IP / DeviceNet Master - Converter
Document code: MN67597_ENG Revision 1.011 Pagina 11 di 25
DeviceNet:
For terminate the CAN line with a 120Ω resistor it is necessary that the Dip1 of ‘Dip-Switch B’ is at ON position.
Cable characteristics:
DC parameter:
Impedance
70 Ohm/m
AC parameters:
Impedance
120 Ohm/m
Delay
5 ns/m
Length
Baud Rate [bps]
Length MAX [m]
125 K
500
250 K
250
500 K
100