User Manual   

CAN from/to Modbus Slave 

 

Document code: MN67412_ENG     Revision 1.000    Page 15 of 25 

 

 

UPDATE DEVICE: 

 
By  pressing  the  “

Update  by  CAN

”  button  from  the  main  window  for  SW67412  (Fig.  2)  the  right 

window appears (Fig. 8). 
 

Note:  
   For  updating  the  device  you  need  the  programmer  “AC67400  -  CAN  Interface  to  configure 

devices”. 
 

 

In order to load the parameters or update the firmware in the gateway, follow these instructions: 

 

Connect  the  “AC67400”  programmer  to  the  PC  through  the  USB  port  and  connect  the  CAN 

port of the “AC67400” to the CAN port of HD67412-Exx-xxx;  

 

Select the “

COM port

” where the “AC67400” is connected (the USB port of the device is see 

like a COM port); 

 

If the BaudRate of CAN is known select it in the field “Select the BaudRate of CAN” otherwise 

you have to select “

Search Baudrate

”; 

 

Press the “

Next

” button; 

 

Select which operations you want to do. You can select only “

Firmware

”, only “

Project

” or 

both of them; 

 

Press the “

Execute update firmware

” button to start the upload; 

 

When  all  the  operations  are  “OK”  the  configuration/firmware  on  the  device  is  correctly 
updated and it is possible to disconnect the “AC67400” programmer. 

 

 

Note:  
    When you install a new version of the software it is better if the first time you do  

the update of the Firmware in the HD67412-Exx-xxx device. 
 

Warning: 
    If  the  Fig.  9  appears  when  you  try  to  do  the  Update  before  require  assistance  try  these 

points: 

 

Check if the serial COM port selected is the correct one; 

 

Check if the CAN cable is connected between the “AC67400” and the device; 

 

Try to repeat the operations for the updating; 

 

Try with another PC; 

 

Try to restart the PC. 

Figure 8: “Update Device” windows

 

Figure 9: “Protection” window

 

Summary of Contents for HD67412-E Series

Page 1: ...Resined optionally Wide supply input range Triple isolation Industrial temperature range 40 C 105 C 22 F 158 F Similiar Products For other Gateways Bridges CAN from to Modbus See also the following l...

Page 2: ...to check that the following document is Updated Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each pa...

Page 3: ...eb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual CAN from to Modbus Slave Document code MN67412_ENG Revision 1 000 Page 3 of 25 CONNECTION SCHEME Figure 1 1 Con...

Page 4: ...ices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual CAN from to Modbus Slave Document code MN67412_ENG Revision 1 000 Page 4 of 25 Figure 1 2 Connection s...

Page 5: ...of 25 POWER SUPPLY The devices can be powered between a wide range of tensions For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax HD67412 Exx xxx 8V 26V 10V 40V Consumption at 24V D...

Page 6: ...ne with a 220 resistor in the HD67412 Exx xxx is made internally of the device when the order is performed If the device have the RS485 terminated the code is the follow HD67412 Exx xYx otherwise is t...

Page 7: ...HD67412 E7x xxx device must be made with a AMP SuperSeal 1 5 Male connector The pinout of Female connector of the board is at right side of the page The termination of CAN line with a 120 resistor in...

Page 8: ...E7x xxx is furnished with 10 cm cable length CONFIGURATION The CAN from to Modbus Slave Gateway allows a CAN network to communicate with a Modbus network You need Compositor SW67412 software on your P...

Page 9: ...To clone the configurations of a Programmable CAN from to Modbus Slave Gateway in order to configure another device in the same manner it is necessary to maintain the folder and all its contents To cl...

Page 10: ...0A or CAN Bus 2 0B TimeOut Data is the maximum time that the device attends for the CAN Frame In the field Modbus Register insert the value of Modbus register which contains the number 1 if a CAN fram...

Page 11: ...12 Fig 2 the window Receive CAN Frame appears Fig 4 A user who has to read a CANbus frame from CANbus to Modbus needs to insert the coordinates of the CANbus frame in order to be transmitted in the fi...

Page 12: ...the field MODBUS there are the modbus words defined for that COB ID Frame In the field Index MODBUS there is the address that contain the Modbus word In the field Selecet Frame Byte you select the po...

Page 13: ...2 Fig 2 the window Transmit CAN Frame appears Fig 6 A user who has to write a CANbus frame from Modbus to CANbus needs to insert the coordinates of the CANbus frame in order to be transmitted in the f...

Page 14: ...the list In the field MODBUS there are the Modbus words defined for that COB ID Frame In the field Index MODBUS there is the address that contain the Modbus word In the field Seleceted Frame Byte you...

Page 15: ...ate of CAN is known select it in the field Select the BaudRate of CAN otherwise you have to select Search Baudrate Press the Next button Select which operations you want to do You can select only Firm...

Page 16: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual CAN from to Modbus Slave Document code MN67412_ENG Revision 1 000 Page 16 of 25 MECHANICA...

Page 17: ...trial Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual CAN from to Modbus Slave Document code MN67412_ENG Revision 1 000 Page 17 of 25 Ty...

Page 18: ...trial Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual CAN from to Modbus Slave Document code MN67412_ENG Revision 1 000 Page 18 of 25 Ty...

Page 19: ...trial Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual CAN from to Modbus Slave Document code MN67412_ENG Revision 1 000 Page 19 of 25 Ty...

Page 20: ...MATIONS The ordering part number is formed by a valid combination of the following HD67412 E y z s d f Fixing lugs A Type 1 B Type 2 C Type 3 RS485 Termination Y Terminated with 220 N Not terminated C...

Page 21: ...minated CAN not terminated and fixing lugs Type C Order Code HD67412 E4V YNA CAN from to Modbus Slave with MiniFit connectors electronic board varnished RS485 not terminated CAN terminated and fixing...

Page 22: ...ated and fixing lugs Type B Order Code HD67412 E4R YNC CAN from to Modbus Slave with MiniFit connectors electronic board resined RS485 not terminated CAN terminated and fixing lugs Type C Order Code H...

Page 23: ...N terminated and fixing lugs Type A Order Code HD67412 E7V YYB CAN from to Modbus Slave with SuperSeal 1 5 connectors electronic board varnished RS485 terminated CAN terminated and fixing lugs Type B...

Page 24: ...s Type B Order Code HD67412 E7R YNC CAN from to Modbus Slave with SuperSeal 1 5 connectors electronic board resined RS485 not terminated CAN terminated and fixing lugs Type C Order Code HD67412 E7R YY...

Page 25: ...uest you need to provide detailed information about the problem 2 Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accept...

Reviews: