________________________________________________________Battery Charger 

                           All specification are subject to change without notice 

 

      INSTRUCTION MANUAL                                                                                               2 

CBI123A_R8 Eng.doc 

 

Rail mounting: 

                                                  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Other modules must have a minimum vertical distance of 10 cm to this power supply in order to guarantee sufficient auto 
convection. 

Use and Connections 

Caution: 

Switch off the system before connecting the module. Never work on the machine when it is live. 

Charging Level Current: 

 With trimmer from 20% to 100% of In. Select the max. battery charge current estimated from 10 to 25% of 

the nominal capacity. 

Battery module (Output 1)  3-4 Pin:  

Battery Input and diagnosi led: very fast blinking= recovery charging ( when the battery is too 

low) , fast blinking=fast charge, slow blinking=trickle charge 

Out Load (Output 2) 1-2 Pin:  

Output voltage 12 Vdc is made via the +,  - . 

Mains or Backup: 

Mains with led off and closed contact (5-6), Backup with led on and closed contact (5-7). 

Note: switching of the relay Backup should be filtered with a delay of at least 5 seconds, example: connection to PLC. 
 

Low Battery or Battery replacement:  

Normal condition with battery OK, led Off and closed contact (8-9), Low Battery with battery 

NOK, led ON and closed contact (8-10), Battery replacement alarm with Power ON , led ON and closed contact (8-10);  (see 
diagnostic Led )  

Life Test Battery 

: In trickle charge condition check every 4 hours, internal impedance (5 blinking  Diagnosis Led) 

Diagnosis Led 

Very fast blinking= recovery charging ( when the battery is too low, Under 10 Vdc) 
Fast blinking= fast charge.  
Slow blinking= trickle charge (floating charge) 
1 blinking= Reverse polarity battery; Bad input voltage battery. 
2 blinking= Battery not connected. 
3 blinking= Short circuit battery element. 
4 blinking= Over Load. 
5 blinking= Bad battery.( Internal impedance Bad or Bad battery wire connection) 

Battery Type Configurations 

 

Position jumper Setting: 

 

Open Lead (Charge): Trickle =2.23 Fast=2.40/cell   

 

 

 

Sealed Lead (Charge): Trickle =2.25 Fast=2.40/cell 

 

  

 

Sealed Lead (Charge): Trickle =2.27 Fast=2.40/cell 

 

 

 

Gel Battery (Charge): Trickle =2.30 Fast=2.40/cell   

 

 

 

Life Test Battery 

 

 

 

 

 

 

 

Caution: 

Switch off the system before Setting the jumper. 

Only jumper in position 5 Refresh ON/OFF state whit Power. 

Notice: 

in the model CBIxxxA/S, without mains voltage,

closing the contact pos. 5 for 1 second and will start-up the 
unit. 

Assembly: pull down the plastic block with 
a screwdriver, place the CB on the rail and 
release the plastic block.  
The CB is now assembled on the rail. 

Disassembly: pull down the plastic block and pullout 
the module like the arrow in the scheme 