background image

 

16 

        

 

 

LEAK TESTING AND EVACUATION 

Charge system with R-410A trace gas and dry nitrogen. 
Pressurize to 150 PSIG.  
Check inside unit, and interconnecting piping with suitable 
leak detector. Recommend GEH10 or equivalent to be used 
for trace gas.  
Release testing charge and connect a good vacuum pump 
to the gauge connections.  
Do not open any other valves at this time.  
Connect a micron gauge to the vacuum pump. 
A deep vacuum of at least 500 microns is required. 
Wait at least 15 minutes, if there is no rise on the micron 
gauge the system is sealed.  
   

!

   

CAUTION: 

 On units with optional Hot Gas Reheat. It 

is necessary to take some additional steps to ensure a 
complete evacuation of the system. The use of two suction 
points will be required due to the complexity of the 
refrigerant circuitry. It is recommended that a suction 
manifold be used at the vacuum pump for evacuation of 
these systems. 

Leaks 

Leaks occur at incorrectly made joints. Very small scratches 
or particles of dirt in a joint can cause a refrigerant leak. 
The leak may be so small that it is difficult to detect on a 
Halide leak detector. Leaks can develop even years after 
the joint is made unless flux and solder specifically 
developed for refrigerant work are used. Any improperly 
made joint will cause trouble in time, as it will eventually 
leak enough refrigerant to reduce capacity of the system. 

Moisture 

Moisture in the refrigeration system will combine with 
fluorine in the refrigerant and form hydrofluoric acid which 
will corrode and pit the system. Hydrofluoric acid also 
decomposes the compressor lubrication oil causing sludge. 
Great care should be exercised in keeping moisture out of 
the refrigeration system when installing tubing, because an 

extremely small amount can cause trouble. For this reason, 
except on large sizes, only refrigeration grade, seamless 
annealed sealed copper tubing should be used. This tubing 
is available at refrigeration supply stores which have been 
dehydrated and cleaned inside and sealed at each end. 
Exposure of the inside of the tubing to the atmosphere must 
be kept to a minimum. Do not use tubing that has been 
exposed. 

Dirt  

Dirt and metal chips must be kept out of the refrigeration 
system, since they will accumulate at strainers and clog 
them, restricting the flow of refrigerant. 

Compressor Oil 

Factory includes compressor oil for the first twenty pounds 
of R410A refrigerant. Compressor oil for change in excess 
of twenty pounds must be provided and added into the 
system in the field. 
The compressor manufacturer stipulates that: 

 For 100% outside air split systems, one additional 

ounce of oil should be added for every two pounds of 
R410A refrigerant charge over the base charge of 
twenty pounds. 

 

For recirculating split systems, one 

additional ounce of 

oil should be added for every five lbs of R410A 
refrigerant charge over the base charge of twenty 
pounds. 

It is recommended that the additional POE oil be added 
while the system is being charged and handling 
practices be carefully followed to prevent the absorption 
of moisture. Interconnecting piping must follow sound 
practices for oil management and be designed so that 
the minimum suction line velocity is at least 1200 fpm 
and the minimum velocity in the liquid line at least 150 
fpm.

Summary of Contents for RCA051

Page 1: ...3 11 4 RCA101 V HCA101 110 5 12 1 RCA141 V HCA141 142 3 11 5 RCA171 V HCA201 187 9 14 7 RCA201 V HCA201 217 0 14 6 RCA271 V HCA271 263 2 13 9 RCA361 V HCA361 311 6 13 3 RCA421 V HCA421 395 5 12 5 95...

Page 2: ...s of the colors used Operational failure of this unit for any reason including but not limited to mechanical or electrical failure of devices internal or external to the unit loss of fuel such as natu...

Page 3: ...rator at the air handling unit as possible The liquid line solenoid is factory installed on units with hot gas reheat Hot Gas Bypass Circuit Provided for capacity control by maintaining a constant suc...

Page 4: ...rive sheaves connected to a 1725 rpm motor The blower has sealed ball bearings that do not require lubrication Blower Motor The blower motor operates at 1725 rpm The motor has sealed ball bearings tha...

Page 5: ...lectric heater may be required Air Handler Model Heater kW Available V HCA051 1 9 V HCA071 1 12 V HCA141 1 25 V HCA201 5 39 V HCA271 5 50 V HCA361 10 60 Minimum 80 CFM per kW Table 4 UNIT LOCATION Con...

Page 6: ...unit support at mounting location Install proper electrical power service and disconnect switch Provide drainage as necessary Maintain minimum clearance for airflow into and out of unit Inspection of...

Page 7: ...1 030 0 5 1 090 0 6 1 160 0 7 1 500 680 0 3 780 0 3 870 0 4 960 0 5 1 040 0 6 1 100 0 7 1 100 650 0 2 770 0 3 860 0 3 940 0 4 1 020 0 5 1 090 0 6 1 160 0 6 VCA HCA 1 400 700 0 3 800 0 3 880 0 4 960 0...

Page 8: ...8 DIMENSIONS...

Page 9: ...9 DIMENSIONS Continued...

Page 10: ...10 DIMENSIONS...

Page 11: ...11 DIMENSIONS Continued...

Page 12: ...LA MCA Max Fuse Size 208 230 1 60 4 4 6 15 208 230 3 60 2 0 3 15 460 3 60 1 0 2 15 1 2 380 415 3 50 1 5 2 15 208 230 1 60 5 4 7 15 208 230 3 60 2 8 4 15 460 3 60 1 4 2 15 3 4 380 415 3 50 2 1 3 15 208...

Page 13: ...conjunction with the control for Hot Gas Reheat A remote system switch such as a timeclock or interlock may be used to energized the controls Once it is established that supply voltage is within the u...

Page 14: ...14 TYPICAL FIELD WIRING DIAGRAM...

Page 15: ...r handler is installed at a higher elevation than the compressor provide a vertical loop in the suction line adjacent to the air handler to a point at least to the top of the evaporator coil Do not in...

Page 16: ...ic acid also decomposes the compressor lubrication oil causing sludge Great care should be exercised in keeping moisture out of the refrigeration system when installing tubing because an extremely sma...

Page 17: ...17 FIELD WIRING DIAGRAM...

Page 18: ...ove 70 75 degrees F Reduce the evaporator load lower entering airflow until the suction pressure lowers to the point at which bypass is desired 115 PSIG If the hot gas bypass was de energized to stop...

Page 19: ...er is applied to the high pressure control and the adjustable time delay The time delay begins when power is applied to the timer After the time delay closes the circuit continues through the low pres...

Page 20: ...er in a commercial split system New system must be evacuated as outlined on page 14 to remove air and non condensables in the system The liquid line drier will trap any moisture left in the system Sys...

Page 21: ...d inlet clearances and for possible air re circulation Check high side equalized pressure reading with equivalent outdoor temperature Check calibration of switch Check discharge and liquid line pressu...

Page 22: ...on of low ambient head pressure control Suction Pressure Too Low Refrigerant undercharge Blower running backwards Loose blower pulley or belts Defective or improperly adjusted expansion valve Dirty fi...

Page 23: ...ilter Check superheat and adjust TXV check bulb Check compressor for proper operation See above high discharge pressure Check external static pressure Supply Air Temperature Too Low Airflow is too low...

Page 24: ......

Page 25: ...__________ WB _________ Design CFM ________________ Outdoor Air Inlet Temperature _____________ DB__________ WB _________ Outdoor Fan Discharge Air Temperature__________ DB ________ Suction Pressure _...

Page 26: ...26 NOTES...

Page 27: ...27 NOTES...

Page 28: ...28...

Reviews: