background image

 

13

 

ELECTRICAL CONTINUED 

 
LOW VOLTAGE WIRING 

Control System Wiring:

 For commercial equipment the 

following table lists the minimum size of 24 volt class 2 
wire to be used.  

 

Ft. Run From Unit to 

Wire Size 

System Switch or Longest Run 

18 AWG 

Maximum Run 50 Feet 

16 AWG 

Maximum Run 75 Feet 

14 AWG 

Maximum Run 100/125 Feet 

14 AWG 

Maximum Run 150/200 Feet 

Table 8 

Due to the complex refrigerant circuitry of these models, 
strict adherence to recommended line sizes and maximum 
line length is required. The maximum wire length shown 
above is not permitted for refrigerant line length. See Table 
9 for recommended refrigerant line sizes and length 
restrictions. 

Temperature Controls:

 The Ambient Compressor 

Thermostat controls compressor on/off operation. The use 
of space or duct mounted sensors to control the 
compressor will produce unpredictable results. On systems 
with optional Hot Gas Reheat a discharge air thermostat is 
mounted in the air handler. A sensor located in the 
conditioned space may be used in conjunction with the 
control for Hot Gas Reheat. A remote system switch such 
as a timeclock or interlock may be used to energized the 
controls. 

Once it is established that supply voltage is within the 
utilization range; check and calculate if an unbalanced 
condition exists between phases.  

Calculate percent voltage unbalance as follows: 

 

 

Percent 

Maximum Voltage Deviation 

 

Voltage = 100x 

From Average Voltage 

 Unbalance 

Average 

Voltage 

 

FOR EXAMPLE - With voltage of 220, 215, and 210 
(Measure L1-L2, L1-L3, L2-L3). 
 

Average voltage = 645 ÷ 3 = 215 

Maximum voltage deviation from 

Average voltage = 220 - 215 = 5 

 
 

Percent 

100 x 5  =  500  

Voltage Unbalance  

  

215    215  = 2.3% 

Percent voltage unbalance must not exceed (2%)  
two percent.  

Contact power company if phase unbalance exceeds 2%. 
A means of disconnecting power from the unit must be 
placed adjacent to the unit in accordance with national 
electrical code or local codes. Aluminum power wire is not 
recommended.

 

 

Note: Wiring –

 Consult the wiring diagram furnished with the unit. These units are custom designed for each application. 

The following wiring diagrams are furnished only as a guide to the installing contractor. The unit wiring diagram is located 
inside the control panel of each unit. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for RCA051

Page 1: ...3 11 4 RCA101 V HCA101 110 5 12 1 RCA141 V HCA141 142 3 11 5 RCA171 V HCA201 187 9 14 7 RCA201 V HCA201 217 0 14 6 RCA271 V HCA271 263 2 13 9 RCA361 V HCA361 311 6 13 3 RCA421 V HCA421 395 5 12 5 95...

Page 2: ...s of the colors used Operational failure of this unit for any reason including but not limited to mechanical or electrical failure of devices internal or external to the unit loss of fuel such as natu...

Page 3: ...rator at the air handling unit as possible The liquid line solenoid is factory installed on units with hot gas reheat Hot Gas Bypass Circuit Provided for capacity control by maintaining a constant suc...

Page 4: ...rive sheaves connected to a 1725 rpm motor The blower has sealed ball bearings that do not require lubrication Blower Motor The blower motor operates at 1725 rpm The motor has sealed ball bearings tha...

Page 5: ...lectric heater may be required Air Handler Model Heater kW Available V HCA051 1 9 V HCA071 1 12 V HCA141 1 25 V HCA201 5 39 V HCA271 5 50 V HCA361 10 60 Minimum 80 CFM per kW Table 4 UNIT LOCATION Con...

Page 6: ...unit support at mounting location Install proper electrical power service and disconnect switch Provide drainage as necessary Maintain minimum clearance for airflow into and out of unit Inspection of...

Page 7: ...1 030 0 5 1 090 0 6 1 160 0 7 1 500 680 0 3 780 0 3 870 0 4 960 0 5 1 040 0 6 1 100 0 7 1 100 650 0 2 770 0 3 860 0 3 940 0 4 1 020 0 5 1 090 0 6 1 160 0 6 VCA HCA 1 400 700 0 3 800 0 3 880 0 4 960 0...

Page 8: ...8 DIMENSIONS...

Page 9: ...9 DIMENSIONS Continued...

Page 10: ...10 DIMENSIONS...

Page 11: ...11 DIMENSIONS Continued...

Page 12: ...LA MCA Max Fuse Size 208 230 1 60 4 4 6 15 208 230 3 60 2 0 3 15 460 3 60 1 0 2 15 1 2 380 415 3 50 1 5 2 15 208 230 1 60 5 4 7 15 208 230 3 60 2 8 4 15 460 3 60 1 4 2 15 3 4 380 415 3 50 2 1 3 15 208...

Page 13: ...conjunction with the control for Hot Gas Reheat A remote system switch such as a timeclock or interlock may be used to energized the controls Once it is established that supply voltage is within the u...

Page 14: ...14 TYPICAL FIELD WIRING DIAGRAM...

Page 15: ...r handler is installed at a higher elevation than the compressor provide a vertical loop in the suction line adjacent to the air handler to a point at least to the top of the evaporator coil Do not in...

Page 16: ...ic acid also decomposes the compressor lubrication oil causing sludge Great care should be exercised in keeping moisture out of the refrigeration system when installing tubing because an extremely sma...

Page 17: ...17 FIELD WIRING DIAGRAM...

Page 18: ...ove 70 75 degrees F Reduce the evaporator load lower entering airflow until the suction pressure lowers to the point at which bypass is desired 115 PSIG If the hot gas bypass was de energized to stop...

Page 19: ...er is applied to the high pressure control and the adjustable time delay The time delay begins when power is applied to the timer After the time delay closes the circuit continues through the low pres...

Page 20: ...er in a commercial split system New system must be evacuated as outlined on page 14 to remove air and non condensables in the system The liquid line drier will trap any moisture left in the system Sys...

Page 21: ...d inlet clearances and for possible air re circulation Check high side equalized pressure reading with equivalent outdoor temperature Check calibration of switch Check discharge and liquid line pressu...

Page 22: ...on of low ambient head pressure control Suction Pressure Too Low Refrigerant undercharge Blower running backwards Loose blower pulley or belts Defective or improperly adjusted expansion valve Dirty fi...

Page 23: ...ilter Check superheat and adjust TXV check bulb Check compressor for proper operation See above high discharge pressure Check external static pressure Supply Air Temperature Too Low Airflow is too low...

Page 24: ......

Page 25: ...__________ WB _________ Design CFM ________________ Outdoor Air Inlet Temperature _____________ DB__________ WB _________ Outdoor Fan Discharge Air Temperature__________ DB ________ Suction Pressure _...

Page 26: ...26 NOTES...

Page 27: ...27 NOTES...

Page 28: ...28...

Reviews: