ENERGY CONSERVATION WHEEL

  

 
Before starting up the unit, check the following:  
1. Does the rotor rotate freely by hand?  
If not, recheck the seal to determine whether or not it is 
binding and if so adjust seals following the instructions 
below.  
2. Is the motor rotation correct?  
This can be checked by detaching the belts from the drive 
sheave and bumping the motor. The sheave should be 
rotating in the direction such that the belt will result in 
rotation per the exterior markings. If not, rewire the motor.  
3.Does the air flow orientation match up to design?  
See the identification markings on the cassette and/or 
refer to the general arrangement drawing to check the four 
duct connections to the unit.  
4. Are the belts on correctly and sufficiently tight?  
Belt length is set by the manufacturer. Consult NovelAire if 
the belt appears too loose.  
5. Is the VFD programmed to control the unit and to 
prevent frost formation?  
If not, follow the instructions in the manual accompanying 
the VFD and/or consult NovelAire.  
 

Seal checks  

The ECW is provided with a neoprene bulb seal which 
provides not only an effective seal in both the peripheral 
and side-to-side sealing directions but also one which is 
easily adjusted to compensate for seal run-in, shipping 
misalignment, etc. The neoprene bulb is  
attached to a metal reinforced U-shaped neoprene grip.  
The metal/neoprene grip allows for an expandable grip 
range which can be moved closer or further from the 
sealing face as needed. The peripheral bulb seals against 
the wheel outer band and the inner bulb seals against the 
wheel face. With the wheel stopped, move seals as close 
to the sealing surface as possible but without exceeding 
grip range of bulb seal and without pressing the bulb  
down against the seal face. Bump the motor. If the motor 
will not turn, the seal is too close and should be nudged 
back where needed. The seal will seek its equilibrium 
position based on the closest part of the sealing face. 
Because the seal is meant to be a non-contact seal, small 
gaps may be seen between seal and sealing surface once 
the equilibrium position is reached. Seal leakage is meant 
to be less than 5% at 1 inch of differential between supply 
and exhaust. Some seal run-in is to be expected, so don't 
be alarmed by small amounts of wear in the neoprene.  
 

Variable speed drive (VFD)  

Check the power supply for proper rating. Make sure that 
the proper jumper orientation is used for the specific 
control input. Make sure that the unit is programmed for 
proper input voltage and output voltage.  
 

Maintenance  

 

Bearings  

Small ECW’s, (smaller than ECW666) are provided with no 
maintenance inboard bearings. These bearings should 
require no maintenance during the life of the equipment. 
Larger ECW’s come equipped with an external flanged  

 
 
bearing which should be greased annually.  Use a 
petroleum based lubricant.  
 

Drive Motor  

The drive motors should require no maintenance.  
Replacement motors may be purchased from normal 
motor distributors such as Grainger, or directly from 
NovelAire if preferred.  
 

Drive Belts  

NovelAire ECW belts are multilink belts with individual 
links constructed of a high performance polyurethane 
elastomer reinforced with multiple plies of polyester fabric. 
This belt provides a strong, yet flexible, belting. The 
multilink feature provides quick, easy servicing or 
replacement. See the Appendix for belt repair/replacement 
instructions.  
 

Seals  

The seals are designed to be durable and require no 
maintenance other than adjustment, but if seals become 
worn or damaged they may easily be replaced. The seals 
are made to clip on the cassette or post metal easily. Call 
NovelAire for servicing information.  
 

Wheel  

The wheel is designed to last the life of the equipment. It 
should be protected by an ASHRAE 30% filter to keep dust 
and dirt from the heat transfer surface. The wheel is 
somewhat self cleaning through its normal action of 
rotating in and out of countercurrent air flow streams. If the 
wheel becomes dirty, it may be cleaned by blowing out the 
unit with compressed air (20 psig maximum). In cases of 
severe filthiness, the wheel may be removed from the 
cassette and washed with water following wheel 
removable procedures outlined below:  
 
1. Remove air handler plenum sections so that the front or 
back of the cassette may be easily accessed and cleared.  
2. Support the wheel from the bottom.  
3. If the unit is equipped with an external flanged bearing, 
loosen the Allen screws in the bearing housing that keeps 
the shaft affixed in the horizontal plane of both bearing, 
front and back. Remove the shaft clips at the face of the 
hub from both sides of the shaft. Unbolt one post 
completely and remove post with bearing completely out. 
Remove the shaft. Roll the wheel carefully out.  
4. If the unit is equipped with an internal bearing, unbolt 
the shaft screw on both sides of the shaft. Unbolt one post 
completely and remove post. Remove the shaft clips at the 
face of the hub from both sides of the shaft. Remove the 
shaft. Roll the wheel out carefully  
5. With the wheel out, wash the media carefully with water. 
Once clean, allow the media to dry out for several hours or 
days if necessary.  
6. Reinstall using the reverse procedure. Run the unit. It 
may take several hours for the desiccant to dry out and for 
the wheel to perform normally.  

Summary of Contents for B

Page 1: ...sate Piping 5 Gas Piping and Venting 5 6 Cooling System Options 6 8 Hot Gas Bypass 6 Head Pressure Control 6 Variable Speed Control 6 Adjustable High and Low Pressure 7 Hot Water Heat Recovery 7 8 Mechanical Adjustments 9 10 Evaporator Blower Fan 9 10 Electrical System Options 10 Air Flow Switch 10 Clogged Filter Indicator 10 Convenience Outlet 10 Exhaust Fan Interlock 10 Power Through the Curb 10...

Page 2: ...e anualmente sus equipos y realice el mantenimiento siempre que sea necesario usando exclusivamente piezas de repuesto de ADDISON Información adicional A través de los distribuidores de Addison está disponible la información sobre aplicaciones guías detalladas sobre diseño de sistemas e instalación y funcionamiento de los productos Por favor contacte con nosotros si necesita más información o si r...

Page 3: ...Product Labeling Signal words are used in combination with colors and or pictures on product labels Following are examples of product labels with explanations of the colors used WARNING Electric Shock Hazard Turn Off All Power Before Servicing DANGER Fire Hazard Use copper wire only Failure to observe could result in property damage bodily injury or death WARNING Cuts and Abrasion Hazard Wear glov...

Page 4: ...vice end and clearance at this point should be maintained A 36 clearance must be allowed for access to the compressor and electrical panel A 24 clearance must be maintained for the air inlet to the condenser coil s Do not locate the unit under an overhang that will short circuit hot air to the coil intakes When installed at ground level the unit should be mounted on a level concrete slab which sho...

Page 5: ...Connections Power wiring should be connected to the main power terminal block located within the unit main control section Power wiring connections on units with factory disconnects should be made at the line side of the disconnect switch Low voltage wiring connections are made to the remote mounted controller or time clock DO NOT TAMPER WITH FACTORY WIRING Contact your local representative or the...

Page 6: ... or metal be provided to prevent any possible damage to the roof If condensate is to be piped into the building drainage system the drain line must penetrate the roof external to the unit Refer to local codes for additional requirements CAUTION Units with high internal and external static pressure drops will require a deeper trap Use the graph and table in Figure 2 GAS PIPING AND VENTING For DC un...

Page 7: ... discharge pressure will permit stable operation in ambients down to 32F The operating pressure switch is adjustable to match customer needs it is factory set to re energize the fans when discharge pressure drops to 295 psig and energize them when pressure increases to 430 psig Variable Speed Control The VARISPEED Fan Control System controls the compressor discharge pressure The speed control modu...

Page 8: ... 0psig 150 psig and is factory set to open at 60 psig and close at 35psig The high pressure switch is adjustable between 200 psig And 610psig and factory set to open at 600psig and to close at 550 psig MECHANICAL ADJUSTMENTS SET FAN RPM All evaporator motor sheaves are set when tested and shipped from the factory Actual rpm must be set and verified with a tachometer Refer to the following Blower P...

Page 9: ...off easily 7 Remove the belt Do NOT pry off belt 8 Loosen set screw s on the outer half of the adjustable pulley 9 The unit has one of two different types of adjustable pulleys 10 Remove key if unit has a keyway type pulley 11 To set the blower for a desired CFM L s first turn the outer half of the adjustable pulley clockwise until it meets the inner half of the pulley 12 Turn the outer half of th...

Page 10: ...a sleeve can be installed in the compressor section to bring power wiring inside the curb preventing a separate roof penetration The sleeve must be sealed after wiring is completed with a suitable mastic to prevent water from entering the space Firestat This control mounted in the return air section de energizes the unit when return air reaches 135 F It is a manual reset control Sure Trip This con...

Page 11: ...ermistor The Electronic solid state control center measures the sensor s change in resistance and sends a varying DC current to the Modulator Regulator valve to adjust the gas input as required 5 The flame sensor proves the presence of the pilot flame generating a DC current of 0 2 microamp or greater to the ignition control The ignition control s internal switch action then de energizes the spark...

Page 12: ...ance Bearings Small ECW s smaller than ECW666 are provided with no maintenance inboard bearings These bearings should require no maintenance during the life of the equipment Larger ECW s come equipped with an external flanged bearing which should be greased annually Use a petroleum based lubricant Drive Motor The drive motors should require no maintenance Replacement motors may be purchased from n...

Page 13: ...dome temperature of the compressor 1 Check crankcase sightglass add oil to bring level to midway in sightglass 2 Check oil pump 3 Check oil failure control for calibration 4 Allow compressor to cool for two hours if compressor is hot Recheck for open circuit 5 Check run capacitor for compressor and fan motor 6 Check subcooling 7 Check for low oil level 7 Check discharge and liquid line pressures c...

Page 14: ...usted expansion valve 4 Check superheat and adjust TXV 5 Dirty filter 5 Check filter and evaporator coil 6 Too little air flow or low entering air temperature 6 Check airflow and entering air wet bulb conditions 7 Restriction in suction or liquid line 7 Check refrigerant circuit for restriction 1 Insufficient refrigerant charge 1 Check subcooling check for leak 2 Defective or improperly adjusted e...

Page 15: ...r motor not running N Supply air temperature too high O Supply air temperature P Liquid line too hot R Suction line frosting Varispeed Condenser Head Pressure Control SYMPTOM POSSIBLE CAUSE REMEDY 1 Input pressure is below operating range 1 No problem normal operation 2 No 24 volt control voltage 2 Check for 24 V AC at control 3 No input pressure to control 3 Check alignment of capillary fitting S...

Page 16: ...al equalizer passage 5 Worn or eroded regulator seat A Erratic pressure control E Regulator fails to close D Regulator will not provide pressure control C Regulator hunting chattering large fluctuations in controlled pressures B Regulator leakage 4 Locate and remove stoppage Install strainer 5 Replace defective part 2 Increase superheat setting Dampen bulb response by repositioning 2 Readjust the ...

Page 17: ...er supply must be 24V AC 2 MR valve installed backward 2 Arrow on MR valve should point in direction of gas flow 2 Install properly 1 Room Override Thermostat if used calls for heat 1 Remove T115 wires from amplifier terminals 3 and 14 1 If proper operation is obtained check thermostat wiring for shorts Rotate thermostat dial above and below room temperature to prove thermostat function 2 Open cir...

Page 18: ...obstruction in gas pipe ahead of controls Increase gas pressure if possible H Incorrect discharge air temperature 1 Calibration 1 Check seal on calibration potentiometer 1 Recalibrate per Temperature Calibration procedure 1 Dirty or sticking plunger 1 Examine Plunger should be clean smooth and operate freely in solenoid sleeve 1 Clean or replace plunger if necessary 2 Loose or broken wiring 2 Insp...

Page 19: ...19 ...

Reviews: