Installation and Safety

INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK
IMPORTANT SAFETY INSTRUCTIONS - PLEASE DO NOT DISCARD THESE INSTRUCTIONS

WARNING – When using electric products, basic precautions should always be followed, including the 
 

following. This manual contains important instructions for Model CoRe+ that shall be 

 

followed during installation, operation and maintenance of the unit. 

Always use a manual screwdriver only; DO NOT use an impact driver for the screws at any times, otherwise, 
it will void the warranty.

Carefully read this guide before installing the EVSE

1-  CAUTION - To reduce the risk of fire, connect only to a circuit provided with 40 amperes maximum branch circuit 
  overcurrent  protection in accordance with the Canadian Electrical Code (CSA C22.1-12) and the National 
 

Electrical Code (ANSI/NFPA 70).

2-  This EVSE was designed to be ground-based, wall-mounted or post-mounted.
3-  You must make sure that the types of mounting surface of the wall or the post will be strong enough to bear the 
 

minimum weight of  the EVSE 15 kg (33 lbs) and their anchors must be compatible with the type of mounting surface.

4-  Verify with local authorities that the location where the EVSE is to be installed is free from underground pipelines 
 

or electrical equipment, otherwise you might inflict yourself serious injuries.

5-  Connect the power supply of the EVSE with caliber 6 to 8 copper conductors rated for usage at a temperature of 
 

at least 75°C.

6-  This product must be connected to a grounded, metal, permanent wiring system, or an equipment-grounding 
 

conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead 

 

on the product and installed by a certified electrician.

7-  Communicate with a certified contractor, certified electrician or trained installer to ensure compliance with local 
 

building code, regulation, security standards and weather conditions.

8-  Any EVSE part alteration will automatically void the warranty.
9-  Handle parts with care, since they can be sharp-edged. Always use safety glasses and gloves when unpacking 
 

and installing.

10- Do not install on or over a combustible surface.
11- The power supply cables of the EVSE shall be rated FT2 minimum.
12- The input cable strain relief, conduit or armed-cable bushings and adapter:
 

 

A. have to be certified for both Canada and US.

 

 

B. have to be waterproof (NEMA 4X).

 

 

C. have to be suitable for the outside diameter of the chosen cable and suitable for mounting into a 34.5 mm 

 

 

  (1,36 in) diameter opening (for connection through the bottom cable opening).

IMPORTANT SAFETY INSTRUCTIONS

This device should be supervised when used around children.
Never insert your finger into the electric vehicle connection.
Never use the EVSE if the flexible power cord or EV cable is frayed, has broken insulation, or any other signs of damage.
Never use the EVSE if the enclosure or the EV connector is broken, cracked, open, or shows any other signs of damage.
This EVSE was designed to be used with electric vehicles equipped with a SAE-J1772 connector.
This EVSE is to be used to charge vehicles that do not require a ventilated environment during charging.
Make sure to always disconnect the power supply of the EVSE before servicing.

Summary of Contents for CoRe+PSV2

Page 1: ...CoRe TM Installation Guide ...

Page 2: ...EVSE part alteration will automatically void the warranty Install the Communication Gateway prior to the Commissioning of the Station The Communication Gateway is the property of AddÉnergie Fees will be charged if the Gateway is damaged or lost IMPORTANT ELEMENTS TO CONSIDER WHEN INSTALLING THE COMMUNICATION GATEWAY An Outdoor installation is recommended The Customer must provide a waterproof PVC ...

Page 3: ...e Subject to Change Amendments and Additions at any Time Without Notice 3 V17 2016 03 03 Table of contents Introduction 4 Statement 5 Installation and Safety 6 Dimensions 7 Wall or Post Mounting 8 Closing the Housing of the Station 11 Preliminary Tests and Commissioning 12 Power Sharing 13 Typical Installation 13 ...

Page 4: ...dance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The enclosed device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions i this device may not ...

Page 5: ... Output connector J 1772 compliant Split Phase 120 240 VAC Supply or 3 phase 120 208 VAC must be protected by a 40A breaker or fuse Maximum output current power CoRe V2 and CoRe VBV2 30A 7 2 kW 240V or 6 3 kW 208V CoRe PSV2 Dynamically controlled by a site controller between 8A and 30A between 1 7 kW et 7 2 kW Built in protection against overvoltage conditions and leakage current to ground Operati...

Page 6: ... rated for usage at a temperature of at least 75 C 6 This product must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the product and installed by a certified electrician 7 Communicate with a certified contractor certified electrician or trained install...

Page 7: ...and Specifications Contained in this Document are Subject to Change Amendments and Additions at any Time Without Notice V17 2016 03 03 Dimensions 154 cm 60 5 47 cm 18 5 33 cm 13 SOL GROUND 19 cm 7 5 14 cm 5 5 130 cm 51 125 9 5 cm 3 75 Patron de perçage Drilling pattern ...

Page 8: ...ng enough to reach the terminal block Connect two power conductors L1 and L2 and the ground conductor GND The grounding conductor shall be provided with green or green and yellow insulation Attach the head base to the wall or the post with appropriate type of anchors Hang the head base to an anchor previously fixed to the wall or post via the keyhole at the top NEVER REMOVE THE PROTECTION PLATE Co...

Page 9: ... the cable connector Replace the plate in place Install the cable connector to the punched hole then the cable Make sure the conductors are long enough to reach the terminal block Connect two power conductors L1 and L2 and the ground conductor GND The grounding conductor shall be provided with green or green and yellow insulation Attach the head base to the wall or the post with appropriate type o...

Page 10: ...pening in the wall or the post IMPORTANT never remove the protection plate of the keyhole Connect two power conductors L1 and L2 and the ground conductor GND The grounding conductor shall be provided with green or green and yellow insulation L1 L2 GND Attach the head base to the wall or the post with appropriate type of anchors Hang the head base to an anchor previously fixed to the wall or post v...

Page 11: ... to Change Amendments and Additions at any Time Without Notice V17 2016 03 03 Closing the Housing of the Station Connect the cables to their connectors Install the head to the base making sure that the seals stay in place then install the four mounting screws Install a o ring to the upper screw O ring Ground Data cable Output ...

Page 12: ... the reader detects the card it will emit an audible bip 2 Immediately after the bip the access card will be authenticated by the charging station 3 If the authentication of the card is successful the automated test of the protection circuit will be performed 4 Once the test is successfully completed the overhead status light will start flashing white 5 If the connector is inserted into an Electri...

Page 13: ...ut to 8A 3 To enable a dynamic sharing of current a site controller must be installed and properly configured by AddÉnergie 4 The site controller will then ensure that available maximum current is shared optimally amongst the charging stations between 8A and 30A for each station while making sure that the maximum circuit capacity 32A in the case of a circuit protected by a 40A breaker is never exc...

Page 14: ...ddenergie ca Installation or commissioning questions 877 505 2674 ext 203 AddÉnergie Technologies Inc Eastern office 2327 Versant Nord Boulevard office 120 Québec QC G1N 4C2 CANADA Central office 7420 Airport Road Mississauga ON L4T 4E5 CANADA Contact Us ...

Reviews: