Installing, Starting and Stopping the
System
3.1
Installing the System
When installing the SR20-FDD into a rack, the selected location should meet environmental
standards as described below.
Rack Space and Airflow Considerations
To allow for adequate airflow, technicians should observe the following space and airflow
requirements when deciding where to install a rack.
• Leave a minimum clearance of 36in (91.4cm) in front of the rack.
• Leave a minimum clearance of 20in (50.8cm) behind the rack.
Temperature Considerations
Your SR20-FDD is designed to operate at room temperature with its self-contained cooling.
Power Considerations
When properly configured and installed the SR20-FDD can draw up to 800 Watts (400 Watts on
average) depending on the number, load, and version of the BioDigitalPC
®
s used.
•
To prevent improper cooling of equipment, do not block the fans.
•
Clean the front fan filters periodically (at least once a month).
•
If the system is intended to operate from an Uninterrupted Power Supply (UPS) power
source, ensure that the UPS unit has enough capacity to run the system.
3.2
Installing the SR20-FDD into a rack
The SR20-FDD does not ship with rack rails. The rails must be provided by the end user; follow
the rail and rack manufacturers installation instructions.
3.3
Installing System Components
BioDigitalPC
®
s are hot-pluggable, meaning technicians do not need to remove power to begin
adding or removing them.
Note
: Only trained technicians are authorized to work inside the SR20-FDD System and access
any of the components inside the system.