ADCP-80-353 • Issue 2 • August 2002 • Section 2: Installation

Page 2-9

©

 2002, ADC Telecommunications, Inc.

The

  REMOTE  ALARMS  terminals  at  the  back  of  the  fuse  panel  provide  a  closed  loop  for

connecting

 cross-connect system fuse failure alarm circuitry to an external alarm system. The

alarm

 will be triggered upon failure of any fuse in the fuse panel. Each GMT fuse also has a

colored

 indicator which is displayed when the fuse is blown, and the fuse panel has an LED

indicator

 which lights when any fuse on the panel is blown.

Figure 2-7. Fuse Panel

3.4

Cross-Connect Jumpers 

When

 installing cross-connect jumpers it is important that congestion be held to a minimum.

This

 will not only simplify installation, but will also provide optimal jumper tracing and ease of

system

 expansion and maintenance.

The

 recommended rules of jumper routing are defined in 

Figure 2-8

.

 The figure shows a three-

bay

  system;  however,  the  same  basic  rules  apply  for  any  number  of  bays.  Cross-connect

jumpers

 should not exceed lengths as described earlier in this section. To prevent unnecessary

buildup

 and congestion, all discontinued cross-connects should be removed from the wireways.

Using

 cross-connect jumpers with accompanying messenger wires, cross-connect all necessary

DSX-4U

 circuits as shown in 

Figure 2-9

.

1. Connect

 the cross-connect OUT (XO) of the first termination to the cross-connect IN (XI)

of

 the second termination. Connect the messenger wire pins of this cross-connect to tracer

lamp

 pin jacks on each termination. Messenger wire pins may be inserted in either of the

pin

 jacks. The two pin jacks on each module are internally connected together.

2. Connect

 the cross-connect IN (XI) of the first termination to the cross-connect OUT (XO)

of

 the second termination. Connect the messenger wire pins of this cross connect to the

remaining

 tracer lamp pin jack on each termination.

ADC

 DSX-4U cross-connect jumpers are available in various lengths from 0.3 to 8.23 m (1 to

27

 feet). It is important to select the proper cable length to prevent congestion. Cross-connect

jumpers

 are also available with one connector factory terminated and one connector kit which is

terminated

  on  site.  This  method  allows  jumpers  to  be  cut  to  the  exact  length  required,

eliminating

 excess jumper buildup.

Disconnect

  any  discontinued  cross-connect  jumpers  at  each  end  and  remove  them  from  the

wireways.

FRONT VIEW

USE

3 AMP

FUSE

MAXIMUM

50 AMP

MAXIMUM

TOTAL BUSS 

AMPERAGE

BLOWN FUSE

INDICATOR

4

8

12

16

2389-B

REAR VIEW

REMOTE ALARMS

NEG (-)

POS (+)

1-10

11-20

1-10

11-20

48V

ONLY

NEG (–)

BUS

POS (+)

BUS

GND

A
B

C

D

E

F

1    2    3    4    5    6   7    8    9    10

Summary of Contents for DSX-4U-24

Page 1: ...ADCP 80 353 Issue 2 August 2002 1021186 Rev B DSX 3 DSX 4U 24 Rear Cross Connect System Installation Guide...

Page 2: ...ADCP 80 353 Issue 2 August 2002 1021186 Rev B DSX 3 DSX 4U 24 Rear Cross Connect System Installation Guide...

Page 3: ...urther disclaims any and all liability for indirect incidental special consequential or other similar damages This disclaimer of liability applies to all products publications and services during and...

Page 4: ...4U Circuit Modules 1 7 4 2 DSX 4U Chassis 1 9 4 3 Fuse Panel 1 9 4 4 Cable Rings and Troughs 1 10 4 5 Cable Brackets 1 10 4 6 Cross Connect System 1 10 5 SYSTEM SPECIFICATIONS 1 10 SECTION 2 INSTALLAT...

Page 5: ...nc TABLE OF CONTENTS Content Page GENERAL INFORMATION 1 WARRANTY SOFTWARE 3 1 2 SOFTWARE SERVICE AGREEMENT 3 1 3 REPAIR EXCHANGE POLICY 3 1 4 REPAIR CHARGES 3 2 5 REPLACEMENT SPARE PRODUCTS 3 2 6 RETU...

Page 6: ...n of possible hazards to persons or equipment An admonishment identifies a possible hazard and then explains what may happen if the hazard is not avoided The admonishments in the form of Dangers Warni...

Page 7: ...53 Issue 2 August 2002 Preface Page vi 2002 ADC Telecommunications Inc DSX 3 DSX 4U 24 REAR CROSS CONNECT SYSTEM USE 3 AMP FUSE MAXIMUM 50 AMP MAXIMUM TOTAL BUSS AMPERAGE BLOWN FUSE INDICATOR 4 8 12 1...

Page 8: ...ovides for test access patch cross connect and monitor functions in 75 ohm digital transmission systems operating with a common signal format and bit rate Bit rates of digital systems in which this cr...

Page 9: ...ndard or midsize coaxial jacks located on the front of the module 2 3 Tracer Lamps A red flashing light emitting diode LED tracer lamp is located at the top of each DSX 4U circuit module for quick and...

Page 10: ...t modules by temporary patch cords The corresponding tracer lamp TL terminals are also jumpered together by the messenger cord in the cross connect cable Cross connected equipments A and B can now be...

Page 11: ...sed of up to ten module chassis each capable of holding up to 24 DSX 4U circuit modules A fuse panel located near the top of the bay supplies power to each chassis Provision for an AC outlet is locate...

Page 12: ...02 Section 1 Description Page 1 5 2002 ADC Telecommunications Inc Figure 1 3 DSX 3 DSX 4U 24 Rear Cross Connect System Bay Front View USE 3 AMP FUSE MAXIMUM 50 AMP MAXIMUM TOTAL BUSS AMPERAGE BLOWN FU...

Page 13: ...4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1 2 3 4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1 2 3 4 5 6 7 8 9 10...

Page 14: ...designed for use with either E1 E3 E4 or STM 1 interfaces however only one type of interface should be terminated at any one cross connect system bay The module has standard or midsize coaxial jacks f...

Page 15: ...or patch access to digital equipment output terminations Any cross connect to the X O jack is disabled and terminated to 75 ohm ground when ever a plug is in the OUT jack IN Midsize Switching Coaxial...

Page 16: ...nstallation 4 3 Fuse Panel The fuse panel as shown in Figure 1 7 provides 48 Vdc power protection for all cross connect system tracer lamp LED circuitry in the bay Power for each DSX 4U chassis is sup...

Page 17: ...an auxiliary source of 110 Vac primary power 5 SYSTEM SPECIFICATIONS Specifications for the DSX 3 DSX 4U 24 Rear Cross Connect System are shown in Table 1 2 Table 1 2 System Specifications PARAMETER S...

Page 18: ...instructions for installing the DSX 3 DSX 4U 24 Rear Cross Connect System It is recommended that the entire section be read and understood before beginning installation 2 OFFICE REQUIREMENTS 2 1 Spac...

Page 19: ...Amp fuse for each DSX 4U chassis in the bay 2 4 Cable Types and Lengths All coaxial cables should be 75 ohm coaxial with tinned copper shield 735A 734A or equivalent The digital equipment terminated a...

Page 20: ...A TYPE 735A TYPE 2 048 252 2 m 827 2 feet 118 2 m 387 9 feet 8 448 135 6 m 444 7 feet 58 1 m 190 7 feet 34 368 158 2 m 518 8 feet 77 3 m 253 6 feet 139 264 73 6m 241 5 feet 36 2 m 118 8 feet 51 84 128...

Page 21: ...9 5 mm 0 375 inch machine screws in the top hole and the fourth hole down on the chassis 4 Using 22 AWG wire connect 48 V and GND from the fuse panel to the respective 48 V and GND terminals on the ba...

Page 22: ...UT X IN CKT 1 2 3 4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1 2 3 4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1...

Page 23: ...to the bay are run vertically along the left side The cables should be run in the rack duct and attached to appropriate cable tie brackets in the duct using nylon tie wraps or cable lacing Any cables...

Page 24: ...ace is shown in Figure 2 6 Terminate each pair of cables from any one office equipment unit to the IN and OUT connectors on any one circuit module Terminate the cable carrying signals to the bay left...

Page 25: ...n BDFB and equipment bay Connect the office power to the bay fuse panel as follows 1 Determine the conductor length from the overhead power supply feeders to the fuse panel power terminals 2 Using 14...

Page 26: ...companying messenger wires cross connect all necessary DSX 4U circuits as shown in Figure 2 9 1 Connect the cross connect OUT XO of the first termination to the cross connect IN XI of the second termi...

Page 27: ...OUTING RULES A All jumpers in the left hand side of the cross connect field should enter and leave the bay from the left vertical wireways B All jumpers in the right hand side of the cross connect fie...

Page 28: ...Apply 48 Vdc office battery at the office distribution panel Cross connect wiring can be checked as necessary by pulling the tracer lamp switch button on any DSX 4U circuit module Pulling of this but...

Page 29: ......

Page 30: ...al fee Contact the Technical Assistance Center at 1 800 366 3891 extension 73475 in U S A or Canada or 952 917 3475 outside U S A and Canada for software service agreement information 3 REPAIR EXCHANG...

Page 31: ...will charge the current price of a field visit plus round trip transportation charges from Minneapolis to the Buyer s site 5 REPLACEMENT SPARE PRODUCTS Replacement parts including but not limited to...

Page 32: ...stance 1 800 366 3891 Extension 73475 ASIA PACIFIC Sales Administration 65 6294 9948 Technical Assistance 65 6393 0739 ELSEWHERE Sales Administration 1 952 938 8080 Technical Assistance 1 952 917 3475...

Page 33: ......

Page 34: ...i www adc com...

Reviews: