ADCP-80-353 • Issue 2 • August 2002 • Section 2: Installation

Page 2-11

©

 2002, ADC Telecommunications, Inc.

Figure 2-9. DSX-4U-24 Cross Connection

4

POWER APPLICATION AND SYSTEM CHECKOUT

Ensure

 that a 0.5 Amp fuse is in place in the fuse panel for each DSX-4U chassis in the bay.

Fuses

 from left to right (as viewed from the front) correlate to chassis from bottom to top, with

one

 fuse for each chassis. Apply –48 Vdc office battery at the office distribution panel.

Cross-connect

 wiring can be checked as necessary by pulling the tracer lamp switch button on

any

 DSX-4U circuit module. Pulling of this button should cause the corresponding tracer lamp

and

 the tracer lamp at the other end of the cross connect to flash for approximately 30 seconds

and

 then remain lit until the button is pushed back in.

XO

XI

O

I

XO

XI

O

I

DSX

CIRCUIT MODULE

(REAR VIEW)

TRACER LAMP

PIN JACKS

TRACER LAMP

PIN JACKS

TL

OUT

CROSS

CONNECTS

CROSS-CONNECT JUMPER

WITH MESSENGER WIRE

IN

OUT

IN

TL

OUT

IN

OUT

IN

8638-B

Summary of Contents for DSX-4U-24

Page 1: ...ADCP 80 353 Issue 2 August 2002 1021186 Rev B DSX 3 DSX 4U 24 Rear Cross Connect System Installation Guide...

Page 2: ...ADCP 80 353 Issue 2 August 2002 1021186 Rev B DSX 3 DSX 4U 24 Rear Cross Connect System Installation Guide...

Page 3: ...urther disclaims any and all liability for indirect incidental special consequential or other similar damages This disclaimer of liability applies to all products publications and services during and...

Page 4: ...4U Circuit Modules 1 7 4 2 DSX 4U Chassis 1 9 4 3 Fuse Panel 1 9 4 4 Cable Rings and Troughs 1 10 4 5 Cable Brackets 1 10 4 6 Cross Connect System 1 10 5 SYSTEM SPECIFICATIONS 1 10 SECTION 2 INSTALLAT...

Page 5: ...nc TABLE OF CONTENTS Content Page GENERAL INFORMATION 1 WARRANTY SOFTWARE 3 1 2 SOFTWARE SERVICE AGREEMENT 3 1 3 REPAIR EXCHANGE POLICY 3 1 4 REPAIR CHARGES 3 2 5 REPLACEMENT SPARE PRODUCTS 3 2 6 RETU...

Page 6: ...n of possible hazards to persons or equipment An admonishment identifies a possible hazard and then explains what may happen if the hazard is not avoided The admonishments in the form of Dangers Warni...

Page 7: ...53 Issue 2 August 2002 Preface Page vi 2002 ADC Telecommunications Inc DSX 3 DSX 4U 24 REAR CROSS CONNECT SYSTEM USE 3 AMP FUSE MAXIMUM 50 AMP MAXIMUM TOTAL BUSS AMPERAGE BLOWN FUSE INDICATOR 4 8 12 1...

Page 8: ...ovides for test access patch cross connect and monitor functions in 75 ohm digital transmission systems operating with a common signal format and bit rate Bit rates of digital systems in which this cr...

Page 9: ...ndard or midsize coaxial jacks located on the front of the module 2 3 Tracer Lamps A red flashing light emitting diode LED tracer lamp is located at the top of each DSX 4U circuit module for quick and...

Page 10: ...t modules by temporary patch cords The corresponding tracer lamp TL terminals are also jumpered together by the messenger cord in the cross connect cable Cross connected equipments A and B can now be...

Page 11: ...sed of up to ten module chassis each capable of holding up to 24 DSX 4U circuit modules A fuse panel located near the top of the bay supplies power to each chassis Provision for an AC outlet is locate...

Page 12: ...02 Section 1 Description Page 1 5 2002 ADC Telecommunications Inc Figure 1 3 DSX 3 DSX 4U 24 Rear Cross Connect System Bay Front View USE 3 AMP FUSE MAXIMUM 50 AMP MAXIMUM TOTAL BUSS AMPERAGE BLOWN FU...

Page 13: ...4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1 2 3 4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1 2 3 4 5 6 7 8 9 10...

Page 14: ...designed for use with either E1 E3 E4 or STM 1 interfaces however only one type of interface should be terminated at any one cross connect system bay The module has standard or midsize coaxial jacks f...

Page 15: ...or patch access to digital equipment output terminations Any cross connect to the X O jack is disabled and terminated to 75 ohm ground when ever a plug is in the OUT jack IN Midsize Switching Coaxial...

Page 16: ...nstallation 4 3 Fuse Panel The fuse panel as shown in Figure 1 7 provides 48 Vdc power protection for all cross connect system tracer lamp LED circuitry in the bay Power for each DSX 4U chassis is sup...

Page 17: ...an auxiliary source of 110 Vac primary power 5 SYSTEM SPECIFICATIONS Specifications for the DSX 3 DSX 4U 24 Rear Cross Connect System are shown in Table 1 2 Table 1 2 System Specifications PARAMETER S...

Page 18: ...instructions for installing the DSX 3 DSX 4U 24 Rear Cross Connect System It is recommended that the entire section be read and understood before beginning installation 2 OFFICE REQUIREMENTS 2 1 Spac...

Page 19: ...Amp fuse for each DSX 4U chassis in the bay 2 4 Cable Types and Lengths All coaxial cables should be 75 ohm coaxial with tinned copper shield 735A 734A or equivalent The digital equipment terminated a...

Page 20: ...A TYPE 735A TYPE 2 048 252 2 m 827 2 feet 118 2 m 387 9 feet 8 448 135 6 m 444 7 feet 58 1 m 190 7 feet 34 368 158 2 m 518 8 feet 77 3 m 253 6 feet 139 264 73 6m 241 5 feet 36 2 m 118 8 feet 51 84 128...

Page 21: ...9 5 mm 0 375 inch machine screws in the top hole and the fourth hole down on the chassis 4 Using 22 AWG wire connect 48 V and GND from the fuse panel to the respective 48 V and GND terminals on the ba...

Page 22: ...UT X IN CKT 1 2 3 4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1 2 3 4 5 6 7 8 9 10 11 12 X OUT X IN CKT 13 14 15 16 17 18 19 20 21 22 23 24 X OUT X IN CKT 1...

Page 23: ...to the bay are run vertically along the left side The cables should be run in the rack duct and attached to appropriate cable tie brackets in the duct using nylon tie wraps or cable lacing Any cables...

Page 24: ...ace is shown in Figure 2 6 Terminate each pair of cables from any one office equipment unit to the IN and OUT connectors on any one circuit module Terminate the cable carrying signals to the bay left...

Page 25: ...n BDFB and equipment bay Connect the office power to the bay fuse panel as follows 1 Determine the conductor length from the overhead power supply feeders to the fuse panel power terminals 2 Using 14...

Page 26: ...companying messenger wires cross connect all necessary DSX 4U circuits as shown in Figure 2 9 1 Connect the cross connect OUT XO of the first termination to the cross connect IN XI of the second termi...

Page 27: ...OUTING RULES A All jumpers in the left hand side of the cross connect field should enter and leave the bay from the left vertical wireways B All jumpers in the right hand side of the cross connect fie...

Page 28: ...Apply 48 Vdc office battery at the office distribution panel Cross connect wiring can be checked as necessary by pulling the tracer lamp switch button on any DSX 4U circuit module Pulling of this but...

Page 29: ......

Page 30: ...al fee Contact the Technical Assistance Center at 1 800 366 3891 extension 73475 in U S A or Canada or 952 917 3475 outside U S A and Canada for software service agreement information 3 REPAIR EXCHANG...

Page 31: ...will charge the current price of a field visit plus round trip transportation charges from Minneapolis to the Buyer s site 5 REPLACEMENT SPARE PRODUCTS Replacement parts including but not limited to...

Page 32: ...stance 1 800 366 3891 Extension 73475 ASIA PACIFIC Sales Administration 65 6294 9948 Technical Assistance 65 6393 0739 ELSEWHERE Sales Administration 1 952 938 8080 Technical Assistance 1 952 917 3475...

Page 33: ......

Page 34: ...i www adc com...

Reviews: