112174-7
www.adclaundry.com
9
To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%. In the example above, when adding louvers or registers,
the 18-inch dimension can be increased by 33% up to 24
inches (18 x 1.3333 = 24). Therefore for a bank of 4 dryers,
2 openings with louvers or registers measuring 24-inches x
23.5-inches (60.96 cm x 59.69 cm) are acceptable. Make-
up air openings should not be located in an area directly
near where exhaust vents exit the building.
Allowances must be made for remote or constricting
passageways or where dryers are located at high altitudes
or predominantly low pressure areas.
IMPORTANT:
Make-up air must be free of dry cleaning
solvent fumes. Make-up air that is contaminated by dry
cleaning solvent fumes will result in irreparable damage to
the motors and other dryer components.
NOTE:
Component failure due to dry cleaning solvent
fumes will void the warranty.
Exhaust Requirements _______________
Exhaust ductwork should be designed and installed by a
qualified professional. Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by the
airflow (sail) switch, burner hi-limits, or lint chamber hi-limit
protector thermostat. The dryer must be installed with a
proper exhaust duct connection to the outside.
A = 18-inches (45.72 cm)
B = 23.5-inches (59.69 cm)
Dryer Enclosure Requirements ______
A
The requirement to allow the dryer door to open completely is
33.5-inches (85.1 cm).
B
A minimum overhead clearance of 12-inches (30.48 cm) is
required.
C
Dryer should be positioned a minimum of 12-inches (30.48 cm)
away from the nearest obstruction. 24-inches (60.96 cm) is
recommended for ease of installation, maintenance, and
service.
D
1/16” (1.5875 mm) minimum is required.
E
Flooring should be level or below dryer cabinet for ease of
removing panels during maintenance.
F
Dryers may be positioned sidewall to sidewall, however a 1/
16” (1.5875 mm) minimum allowance must be made for the
opening and closing of the control door, along with the removal
of panels during maintenance.
G
4-inch (10.16 cm) maximum.
Fresh Air Supply Requirements ______
This appliance may only be installed in a room that meets
the appropriate ventilation requirements specified in the
national installation regulations.
When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of
the building. Therefore, the room air must be continually
replenished from the outdoors. If the make-up air is
inadequate, drying time and drying efficiency will be adversely
affected. Ignition problems and sail switch “fluttering”
problems may result, as well as premature motor failure from
overheating. The dryer must be installed with provisions for
adequate combustion and make-up air supply.
Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer. Fresh air
ventilation openings shall not be blocked and/or sealed. As
a general rule, an unrestricted air entrance from the outdoors
of 212 inch
2
(1,367 cm
2
) is required for each dryer. (Based
on 1 inch
2
[6.5 cm
2
] per 1,000 Btu [252 kcal].)
It is not necessary to have a separate make-up air opening
for each dryer. Common make-up air openings are
acceptable. However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.
EXAMPLE: For a bank of four dryers supplied by the
openings: 4 dryers x 212 inch
2
per dryer = 848 inch
2
total
848 inch
2
÷ 2 openings = 424 inch
2
per opening.
424 inch
2
= 18 inch x 23.5 inch.
Therefore: for a bank of four dryers, 2 unrestricted openings
measuring 18-inches by 23.5-inches (45.72 cm by 59.69 cm)
are acceptable.
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in
death or fire.
!
WARNING
Summary of Contents for AD-444
Page 20: ...ADC Part No 112174 7 09 02 14 ...