background image

112174-7

www.adclaundry.com

9

To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%.  In the example above, when adding louvers or registers,
the 18-inch dimension can be increased by 33% up to 24
inches (18 x 1.3333 = 24).  Therefore for a bank of 4 dryers,
2 openings with louvers or registers measuring 24-inches x
23.5-inches (60.96 cm x  59.69 cm) are acceptable.  Make-
up air openings should not be located in an area directly
near where exhaust vents exit the building.
Allowances must be made for remote or constricting
passageways or where dryers are located at high altitudes
or predominantly low pressure areas.

IMPORTANT:

 Make-up air must be free of dry cleaning

solvent fumes.  Make-up air that is contaminated by dry
cleaning solvent fumes will result in irreparable damage to
the motors and other dryer components.

NOTE:

 

Component failure due to dry cleaning solvent

fumes will void the warranty.

Exhaust Requirements _______________

Exhaust ductwork should be designed and installed by a
qualified professional.  Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by the
airflow (sail) switch, burner hi-limits, or lint chamber hi-limit
protector thermostat.  The dryer must be installed with a
proper exhaust duct connection to the outside.

A = 18-inches (45.72 cm)
B = 23.5-inches (59.69 cm)

Dryer Enclosure Requirements ______

 A

The requirement to allow the dryer door to open completely is
33.5-inches (85.1 cm).

B

A minimum overhead clearance of 12-inches (30.48 cm) is
required.

C

Dryer should be positioned a minimum of 12-inches (30.48 cm)
away from the nearest obstruction.  24-inches (60.96 cm) is
recommended for ease of installation, maintenance, and
service.

D

1/16” (1.5875 mm) minimum is required.

E

Flooring should be level or below dryer cabinet for ease of
removing panels during maintenance.

F

Dryers may be positioned sidewall to sidewall, however a 1/
16” (1.5875 mm) minimum allowance must be made for the
opening and closing of the control door, along with the removal
of panels during maintenance.

G

4-inch (10.16 cm) maximum.

Fresh Air Supply Requirements ______

This appliance may only be installed in a room that meets
the appropriate ventilation requirements specified in the
national installation regulations.
When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of
the building.  Therefore, the room air must be continually
replenished from the outdoors.  If the make-up air is
inadequate, drying time and drying efficiency will be adversely
affected.  Ignition problems and sail switch “fluttering”
problems may result, as well as premature motor failure from
overheating.  The dryer must be installed with provisions for
adequate combustion and make-up air supply.
Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer.  Fresh air
ventilation openings shall not be blocked and/or sealed.  As
a general rule, an unrestricted air entrance from the outdoors
of 212 inch

2

 (1,367 cm

2

) is required for each dryer.  (Based

on 1 inch

2

 [6.5 cm

2

] per 1,000 Btu [252 kcal].)

It is not necessary to have a separate make-up air opening
for each dryer.  Common make-up air openings are
acceptable.  However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.
EXAMPLE: For a bank of four dryers supplied by the
openings: 4 dryers x 212 inch

2

 per dryer = 848 inch

2

 total

848 inch

2

 ÷ 2 openings = 424 inch

2

 per opening.

424 inch

2

 = 18 inch x 23.5 inch.

Therefore: for a bank of four dryers, 2 unrestricted openings
measuring 18-inches by 23.5-inches (45.72 cm by 59.69 cm)
are acceptable.

Fire Hazard

Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in
death or fire.

!

 WARNING

Summary of Contents for AD-444

Page 1: ...s supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier AVERTISSEMENT Assurez vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres v...

Page 2: ...__________________________________________ ____________________________________________________________________________________________________ Replacement parts can be obtained from your reseller or the ADC factory When ordering replacement parts from the factory you can FAX your order to ADC at 1 508 678 9447 or telephone your order directly to the ADC Parts Department at 1 508 678 9000 Please s...

Page 3: ...ld be supervised if near dryer s in operation Under no circumstances should the dryer door switch lint door switch or heat safety circuit ever be disabled Do not modify this appliance The dryer must never be operated with any of the back guards outer tops or service panels removed Personal injury or fire could result The dryer must never be operated without the lint filter screen in place even if ...

Page 4: ...rubber and also may be a fire hazard The possible presence of residual quantities of aggressive or decomposed chemicals in the load may produce damage to the machine and harmful fumes A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer The frequency of inspection and cleaning can best be determined from e...

Page 5: ...__________________________________________________________________________________ ___________________________________________________________________________________________________________________________________ ___________________________________________________________________________________________________________________________________ _____________________________________________________...

Page 6: ...10 Optional 2 20 32 cm 1 25 4 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 1 2 VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW PER POCKET EXHAUST CONNECTION DIAMETER PER POCKET COMPRESSED AIR CONNECTION COMPRESSED AIR VOLUME OVEN SIZE PER POCKET kW Btu hr kcal hr VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE...

Page 7: ...dclaundry com 7 Specifications _____________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Page 8: ...ing will be necessary The dryer must be installed with adequate clearance for air openings into the combustion chamber IMPORTANT The dryer must be installed in a location environment which the ambient temperature remains between 40 F 4 44 C and 130 F 54 44 C WARNING Excessive Weight Hazard Use two or more people and mechanical equipment to lift move and install dryer Failure to do so can result in...

Page 9: ...g should be level or below dryer cabinet for ease of removing panels during maintenance F Dryers may be positioned sidewall to sidewall however a 1 16 1 5875 mm minimum allowance must be made for the opening and closing of the control door along with the removal of panels during maintenance G 4 inch 10 16 cm maximum Fresh Air Supply Requirements ______ This appliance may only be installed in a roo...

Page 10: ...0 6 in WC 1 48 mb NOTE When the exhaust ductwork passes through a wall ceiling or roof made of combustible materials the opening must be 2 inches 5 08 cm larger than the duct all the way around The duct must be centered within this opening The ductwork for this dryer must be suitable for the appliance category in accordance with national installation regulations of the country of destination Outsi...

Page 11: ...t to the nearest obstruction The length of the ductwork from the dryer to the outside exhaust outlet must not exceed 20 feet 6 09 meters The minimum diameter of this ductwork must be at least 8 inches 20 32 cm when each pocket tumbler is vented individually and 10 inches 25 4 cm when both pockets tumblers are combined Including tumbler dryer elbow connections or elbows used for outside protection ...

Page 12: ...rounding must conform to applicable requirements of the National Electrical Code ANSI NFPA NO 70 LATEST EDITION or in Canada the installation must conform to applicable Canada Standards Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION The ground connection may be to a proven earth ground at the location service panel For added personal safety when possible it is suggested that ...

Page 13: ...system at test pressures in excess of 1 2 psig 3 5 kPa The dryer must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than 1 2 psig 3 5 kPa IMPORTANT Failure to isolate or disconnect the dryer from supply as noted can cause irreparable damage to the gas valve voiding...

Page 14: ...as shutoff valve be provided to the gas supply line of each dryer for ease in servicing IMPORTANT When plumbing upper and lower tumblers together as illustrated below supply connection must be a minimum of 3 4 19 05 mm An 1 8 N P T plugged tap accessible for a test gauge connection must be installed in the main gas supply line immediately upstream of each dryer IMPORTANT Pipe joint compounds that ...

Page 15: ...ls and service box covers have been replaced Check the lint door to ensure that it is closed and secured in place Rotate the tumbler by hand to be sure it moves freely Preoperational Test __________________ All dryers are thoroughly tested and inspected before leaving the factory However a preoperational test should be performed before the dryer is publicly used It is possible that adjustments hav...

Page 16: ... open the main door Continuation of the cycle will resume only after the door has been closed and any of the three temperature selection buttons is pressed Upon completion of the drying and cooling cycles the tone buzzer will sound and the dryer will go into the Anti Wrinkle Mode if active for up to 99 minutes or until the main door or lint drawer has been opened IMPORTANT For more detailed inform...

Page 17: ...in writing either by FAX or CERTIFIED MAIL Return Receipt Requested as to the information necessary to process claim If reply is not received by the Warranty Department within 30 days from the FAX letter date then no replacements credits or refunds will be issued and the merchandise will be discarded Routine Maintenance ________________ Cleaning A program and or schedule should be established for ...

Page 18: ...rmostats Lubrication The motor bearings and under normal most conditions the tumbler bearings are permanently lubricated It is physically possible to relubricate the tumbler bearings if you choose to do so even though this practice is not necessary Use Shell Alvania 2 grease or its equivalent The tumbler bearings used in the dryer do not have a grease fitting Provisions are made in the bearing hou...

Page 19: ...____________________________________________________ _____________________________________________________________ _____________________________________________________________ _____________________________________________________________ _____________________________________________________________ _____________________________________________________________ _____________________________________...

Page 20: ...ADC Part No 112174 7 09 02 14 ...

Reviews: