16
American Dryer Corp.
113354 - 23
IMPORTANT: Make-up air must be provided from a source free of dry cleaning solvent fumes.
Make-up air that is contaminated by dry cleaning solvent fumes will result in
irreparable damage to the motors and other dryer components.
NOTE: Component failure due to dry cleaning solvent fumes will VOID THE WARRANTY.
D. FRESH AIR SUPPLY REQUIREMENTS
This appliance may only be installed in a room that meets the appropriate ventilation requirements specified in
the national installation regulations.
When the dryer is operating, it draws in room air, heats it, passes this air through the tumbler, and exhausts it out
of the building. Therefore, the room air must be continually replenished from the outdoors. If the make-up air
is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and sail switch
“fluttering” problems may result, as well as premature motor failure from overheating.
Air supply (make-up air) must be given careful consideration to ensure proper performance of each dryer. An
unrestricted source of air is necessary for each dryer. As a general rule, an unrestricted air entrance from the
outdoors (atmosphere) of a minimum of 4.5 square feet (0.41 square meters) is required for each dryer. (Based
on 1 square inch per 1,000 Btu.)
To compensate for the use of registers or louvers used over the openings, this make-up air must be increased by
approximately thirty-three percent (33%). Make-up air openings should not be located in an area directly near
where exhaust vents exit the building. It is not necessary to have a separate make-up air opening for each dryer.
Common make-up air openings are acceptable. However, they must be set up in such a manner that the
make-up air is distributed equally to ALL the dryers. The dryer must be installed with provisions for adequate
combustion and make-up air supply.
EXAMPLE: For a bank of six (6) dryers, two (2) unrestricted openings measuring 3 feet by 4.5 feet (0.91 meters
by 1.37 meters) are acceptable.
Allowances must be made for remote or constricting passageways or where dryers are located at excessive
altitudes or predominantly low pressure areas.