2.4.4 Individual Cutout Wiring
The CCR and load sides of the cutout are clearly marked and must not be reversed. See Figure 10.
Figure 10:
CCR-Side (Input) and Load-Side (Output) Symbols
To wire the SCO cutout, perform the following procedure:
1. See Figure 2. Unlock the lock (if depressed) using the key (4) and remove the cover (1).
2. See Figures 6 and 11. If required, wire the interlock switch. The interlock switch is used to further reduce the risk that the CCR
is turned on when the CCR is in remote control.
The interlock switch is connected between the CCI terminal (the remote control power source) and the CC terminal (the ON
remote control command).
CAUTION
SCO cutouts should not be wired in any manner other than described in this manual without the approval of ADB
Airfield Solutions.
Input (CCR)
Side Symbol
Output (Load)
Side Symbol