Sign Load & Transformer Requirements
In the table below, the number for the total VA load imposed on the CCR represents the actual load imposed on the regulator
and accounts for power factor and load imposed by the L-830 transformer.
Low VA Halogen Lamps
Sign Size
No. of Modules
Trans-
former
No. of Lamps
Sign Power Factor
Volt Amp VA Load
48 Watt Lamps — Style 2, 3-Step Signs (4.8 - 6.6 A)
1
1
100 W
1
0.98
106
1
2
200 W
2
0.99
155
1
3
300 W
3
0.98
202
1
4
300 W
4
0.99
250
2, 3
1
200 W
2
0.99
155
2, 3
2
300 W
4
0.99
250
2, 3
3
500 W
6
0.98
340
2, 3
4
300 W (2)
8
0.97
450
4
1
300 W
4
0.99
250
5
1
200 W
2
0.99
155
Low VA Halogen Lamps
Sign Size
No. of Modules
Trans-
former
No. of Lamps
Sign Power Factor
Volt Amp VA Load
48 Watt Lamps — Style 3, 5-Step Signs (2.8 - 6.6 A)
1
1
200 W
1
0.97
105
1
2
300 W
2
0.98
145
1
3
500 W
3
0.98
190
1
4
500 W
4
0.98
233
2, 3
1
300 W
2
0.98
145
2, 3
2
500 W
4
0.98
233
2, 3
3
500 & 300 W
6
0.98
350
2, 3
4
500 W (2)
8
0.97
440
4
1
500 W
4
0.98
233
5
1
300 W
2
0.98
145
Low VA Halogen Lamps
Sign Size
No. of Modules
Trans-
former
No. of Lamps
Sign Power Factor
Volt Amp VA Load
48 Watt Lamps — Style 5 Signs (5.5 A)
1
1
45 W
*
1
0.99
48
1
2
100W
2
0.99
96
1
3
200 W
3
0.99
144
1
4
200 W
4
0.99
192
2, 3
1
100 W
2
0.99
96
96A0286, Rev. AT, 2020/09/16
11
Copyright
©
ADB Safegate, All Rights Reserved
Summary of Contents for L-858 AGSF Series
Page 1: ...L 858 AGSF Incandescent Airfield Guidance Signs FAA User Manual 96A0286 Rev AT 2020 09 16 ...
Page 2: ......
Page 8: ...L 858 AGSF List of Figures viii Copyright ADB Safegate All Rights Reserved ...
Page 10: ...L 858 AGSF List of Tables x Copyright ADB Safegate All Rights Reserved ...
Page 16: ...L 858 AGSF Safety 6 Copyright ADB Safegate All Rights Reserved ...
Page 56: ......