Installation
© ADB SAFEGATE All Rights Reserved
16
96A0481 Rev. A
2.3.4 Earth Grounding
To protect it against a surge generated by lightning, each AGLAS Remote should be provided with a separate, low induction and
low resistance ground connection via the ground screw. The ground cable must be connected to the ground screw by means of a
suitable cable lug. The cross-sectional area of the cable should be at least AWG 8 (6 mm
2
) with a maximum cable length of 36-
inch (1m).
If the isolation value of the earth ground is bad, it is better NOT to connect the remote to earth ground (see Figure 11).
Figure 11:
Connection to a series circuit isolation transformer and light fitting
2.3.5 Safety Instructions
NOTE:
The AGLAS Remote is maintenance free.
The AGLAS Remote must never be opened, otherwise warranty will be void.
DANGER
Work on 120/240 V power supply systems or the series circuit must only be carried out by trained, qualified staff.
The currently applicable regulations according to international standards must be followed.
See also “Safety” on page 1