EN
6.2 - Daily use
- If hoses are used, make sure the ends are properly connected to the tanks. Firmly hold the end of the discharge pipe to prevent
accidental spillage.
- Before starting the pump, make sure the discharge valve or the nozzle is closed.
- When you are ready, switch the pump on. The pump can remain in bypass (internal circulation if the discharge is closed) only for
brief periods.
- With the pump on and in bypass, open the discharge valve or nozzle holding it firmly.
- When you have finished dispensing, close the valve or nozzle and switch the pump off.
6.3 - Noise level
Under normal operating conditions the noise emitted by all models does not exceed 80 dB at a distance of 1 metre
from the electric pump.
CAUTION! Operation of the pump with discharge closed is allowed only for brief periods (max 1-2
minutes).
Make sure the pump is switched off after use.
If there is a power failure:
1. Close the discharge valve or nozzle
2. Put the end of the discharge pipe into its housing on the tank
3. Switch the pump OFF
When the power has returned, restart the pump as described at the beginning of the section.
6.4 - Compatibility in an electromagnetic environment
The machine is designed to operate correctly in an industrial electromagnetic environment, and staying within the Emission
and Immunity limits laid down in the following Harmonised Standards:
IEC EN 61000-6-2
Electromagnetic compatibility (EMC) - Generic standards – Immunity for industrial environments
IEC EN 61000-6-4
Electromagnetic compatibility (EMC) - Generic standards – Emission standard for industrial
environments
7 - TROUBLESHOOTING
PROBLEM POSSIBLE CAUSE
CORRECTIVE ACTION
THE PUMP
DOES NOT
START UP
Power failure
Check the electrical connections and the safety
devices
The circuit breaker has tripped
Use the electric pump in the recommended operating
conditions and according to its intended use (chap.
2 - chap. 5)
Impeller blocked
Make sure there are no obstructions in the pump body
or along the suction and discharge lines
Defective motor
Contact the dealer (fault code M1)
PUMP IS
VERY NOISY
Cavitation
Reduce the negative suction pressure
Make sure there are no leaks or restrictions on the
suction part (recommended pipes chap. 5.2)
Air in the hydraulic circuit
Make sure there are no suction leaks
Dispense to bleed the air from the circuit
LIQUID LEAK Clamps loosened
Make sure all clamps are properly tightened
Gaskets worn
Replace the worn gaskets
Non-compatible liquids used
Check compatibility of the fluid used (chap. 3.3)
Shaft seal ring dirty or damaged
Contact the dealer (fault code A1)