INSTALLATION
CALCULATION OF THE FLUE PIPE LENGTH
When connecting the flue pipes, make sure not to exceed the maximum flue pressure drop
value, or the maximum length in meters of straight pipes recommended for the product,
otherwise the system pressure might decrease.
The flue pipe dimensions can be calculated using the following tables, indicating the corresponding length
in meters of straight pipes, applied to each of the connection components, as well as the pressure drop
value per component. Then compare the calculation result to the recommended maximum flue pipe length
or maximum pressure drop value for each type of Compact Condens model.
The following tables are based on ACV equipment and cannot be applied as a rule.
Equivalent length (in m)
Pipe diameter
Ø 200 mm
Ø 180 mm
Ø 150
Ø 110
1 m straight pipe
1
1
1
1
90° elbow
5.75
4.5
4.0
3.5
45° elbow
3.75
2.5
1.7
1.5
Maximum length (in meters) for C63 connection type
Model
Max.
allowed
pressure
drop
Parallel air/flue
gas
Ø110/200
Parallel air/flue
gas
Ø180/180
Parallel air/flue
gas
Ø150/200
Parallel air/flue
gas
Ø200/200
170
150 Pa
13 m
112 m
83 m
—
210
150 Pa
9 m
75 m
53 m
120 m
250
150 Pa
6 m
45 m
36 m
82 m
300
150 Pa
4 m
33 m
26 m
60 m
Pressure drop (Pa) per component
Model
150
210
250
300
Component
Flue
Air
Flue
Air
Flue
Air
Flue
Air
Straight pipe (1m)
Ø200 mm
0.4
0.7
1.0
1.4
Ø150 mm
1.4
2.1
3.1
4.2
Elbow (90°)
Ø200 mm
2.5
4.0
5.7
7.8
Ø150 mm
5.3
8.3
12.0
16.4
Elbow (45°)
Ø200 mm
1.7
2.6
3.7
5.1
Ø150 mm
2.3
3.5
5.1
6.9
C33 Terminal
Ø200 mm
16.4
25.7
36.9
50.3
Ø150 mm
B23 Terminal
Ø200 mm
4.7
7.4
10.6
14.5
C53 Terminal
Ø200 mm
7.4
16.4
7.4
25.7
10.6
37.0
14.5
50.3
Ø150 mm
Condensate trap
Ø200 mm T +
Bend 90°
5.0
8.0
11.4
15.4
Expander
110/150mm
0.7
1.0
1.5
2.1