SAFETY INSTRUCTIONS FOR THE INSTALLATION
General remark
•
The connections (electrical, flue pipe, hydraulic, gas/fuel) must be carried out in
accordance with current standards and regulations in force.
Essential recommendations for the correct operation of the appliance
•
The boiler must be installed in a dry and protected area, with an ambient
temperature comprised between 0 and 45°C.
•
Install the appliance to ensure easy access at all times.
•
Make sure that the mains water used to fill the boiler has a minimum pressure of
1.2 bar.
•
Make sure to install a pressure reducing valve set at 4.5 bar if the mains supply
pressure is in excess of 6 bar.
•
If works need to be performed (in the boiler room or close to the air vents), make
sure to turn off the boiler to prevent dust from entering and accumulating in the
boiler heating system.
Essential recommendations for safety
•
Install the boiler on a base made of non-combustible materials.
•
Do not store any corrosive products, paint, solvents, salts, chloride products and
other detergent products near the appliance.
•
Make sure that all air vents are unobstructed at all times.
•
A condensation outlet connected to the sewer must be fitted close to the boiler to
prevent the condensation products from the flue pipe from running into the boiler.
•
Install a condensate neutralisation system if required by national and/or local
regulations and have it cleaned regularly.
•
The horizontal flue pipes must be installed with a slight slope of 5 cm per meter,
so that the acid condensation water flows to a condensate recovery container and
does not damage the heating body.
•
Only use ACV flue systems to connect this appliance to ensure that the pipe and
connection diameters all match.
Essential recommendations for the electrical safety
•
Only an approved installer is authorized to carry out the electrical connections.
•
Install a 2-way switch and a fuse or circuit breaker of the recommended rating
outside the appliance, so as to be able to shut power down when servicing the
appliance or before performing any operation on it.
•
Isolate the external electrical supply of the appliance before performing any
operation on the electrical circuit.
•
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless supervised or unless they have been given instruction concerning the use
of the appliance by a person responsible for their safety.
TOOLS REQUIRED FOR THE INSTALLATION
GAS
pressure
(mbar)
Compact Condens : A1003043 - 664Y7200 • A
en
22
EN
FR
NL
ES
IT
DE
PL
RU
INSTALLATION
PACKAGE CONTENTS
The Compact Condens boilers are delivered assembled and packaged.
At product reception and after removal of packaging, check the package contents and that
the appliance is free of damages.
Contents
•
Boiler
•
Installation, Operation and Maintenance Instructions, for the User and the Installer
BOILER PREPARATION
1.
Remove the sealing/protection caps from the connection tubes. Some dirty water might come out.
2.
Fill the condensate trap with water by pouring some water into the cast aluminium exhaust con-
nection at the back.
3.
Make all the required electrical connections of accessories (pumps, thermostats, etc.). Refer to “Wir-
ing Diagram and Electrical Connections” on page 18.