OPERATIONAL SETTINGS

WSX D 

INSTRUCTION 

SHEET 

PAGE 3

2 = Occupancy Time Delay

The length of time an occupancy sensor will keep the lights on after it last detects occupancy.

**Test mode sets Occupancy Time Delay to 30 seconds, and increases photocell transition rate 
in addition to disabling the microphone on units with Dual Technology.   

3 = On Mode

Automatic On

Sensor automatically turns the lights on when it detects occupancy. 

Manual On

Sensor requires pressing the button to turn the lights on. 

Reduced Turn-On 

Sensor is set to initially only detect large motions, effectively ignoring any reflected Passive 
Infrared (PIR) signals. Occupants will still be detected immediately when they enter the room as 
their PIR signal is large. Once lights are on, the sensor returns to maximum sensitivity.

4 = Switch Modes

Switch Enable (Override Off)

Button will turn lights off and keep them off until pressed again. The lights will remain off until 
the button is pressed again, restoring the sensor to Automatic On mode. 

Switch Disable 

User is prevented from turning off the lights via the push-button. 

Predictive Mode

Pressing the push-button switch overrides the lights off and temporarily disables the occupancy 
detection. After 10 seconds, the occupancy detection reactivates and monitors for an additional 
30 seconds. If no occupancy is detected during this period, the sensor will revert to Automatic On 
operation. If occupancy is detected, the sensor will remain in Override Off mode and requires the 
switch to be pressed again in order to restore the sensor to Automatic On. 

Predictive Mode with Expiration

Pressing the push-button switch overrides the lights off and temporarily disables the occupancy 
detection. After 10 seconds, the occupancy detection reactivates and monitors for an additional 
30 seconds. If no occupancy is detected during this period, the sensor will revert to Automatic 
On operation.

5 = Darkness Set-Point / Inhibit Set-Point

 The ambient light level at which the sensor sets the lights to the High Trim setting.

**Set Now will automatically select the Darkness Set-Point based on the current conditions 
in the room. Lights will go to full bright and sensor will rapid flash for 15 seconds allowing 
occupant to move out of direct view of sensor. Once the set-point selection is completed, the 
sensor will double-blink in confirmation.     

6 = Daylight Set-Point

The ambient light level at which the sensor sets the lights to the Low Trim setting.  

**Set Now will automatically select the Daylight Set-Point based on the current conditions 
in the room. Lights will go to full dim and sensor will rapid flash for 15 seconds allowing 
occupant to move out of direct view of sensor. Once the set-point selection is completed, the 
sensor will double-blink in confirmation. 

7 = Photocell Mode

Inhibit Only

Prevents lights from automatically coming on when light level is above the Inhibit Set-Point

Adaptive Daylight Harvesting

Dims lights from high trim to low trim setting according to Darkness and Daylight set-points.

8 = Dim to Off Occupancy Time Delay

After the Occupancy Time Delay (Function 2) has expired, this setting specifies the amount of 
time lights are held at Low Trim (Function 16) before turning off.

9 = Restore Defaults

Returns all functions to original settings.

10 = Minimum On Time

Required initial time for lamps to be on after each switch on, regardless of occupancy status. 
Once met, lights resume following occupancy time delay.

11 = LED Operation

Indicates behavior of device’s LED.

 

12 = Dual Technology (Microphonics™)

The secondary method of occupancy detection that allows the sensor to hear occupants.

13 = Microphone Grace Period

Time period after lights are automatically turned off that they can be voice reactivated.

14 = Manual On Grace Period

Time period after lights automatically turn off that they can be reactivated by motion. Applicable 
only when sensor is in Manual On (Semi Auto) mode.

15 = Dimming Range Max (High Trim)

The maximum output level of the sensor.

**Default for EZ option

16 = Dimming Range Min (Low Trim)

The minimum output level of the sensor.

**Default for EZ option

17 = Predictive Exit Time

Time period after manually switching lights off for occupant to leave the space. Applicable only 
when sensor is in Predictive Off mode.

18 = Predictive Grace Time

Time period after Predictive Exit Time that sensor rescans the room for remaining occupants. 
Applicable only when sensor is in Predictive Off mode.

19 = Fade On Rate

Time required for light to reach preset level.

20 = Fade Off Rate

Time required for light to turn Off.

21 = Start Level

Level of light output when occupancy is initially detected. Not applicable in Automatic Dimming 
Control (ADH) mode.

1 - Maintain Current*

2 - Restore Defaults

1 - Occupancy Indication*

2 - Disabled

1 - 0.75 sec*

3 - 5 sec

2 - 2.5 sec

4 - 15 sec

1 - 0.75 sec

3 - 5 sec

2 - 2.5 sec*

4 - 15 sec

1 - Test Mode**

5 - 7.5 min

9 - 17.5 min

13 - 27.5 min

2 - 30 sec

6 - 10.0 min*

10 - 20.0 min

14 - 30.0 min

3 - 2.5 min

7 - 12.5 min

11 - 22.5 min

4 - 5.0 min

8 - 15.0 min

12 - 25.0 min

1 - Automatic On*

3 - Reduced Turn-On

2 - Manual On

1 - Switch Enable

3 - Predictive Mode

2 - Switch Disable

4 - Predictive Mode with Expiration*

1 - Disabled*

3 - Adaptive Daylight Harvesting

2 - Inhibit Only

1 - 0  sec*

5 - 7.5 min

9 - 17.5 min

2 - 30 sec

6 - 10 min

10 - 20 min

3 - 2.5 min

7 - 12.5 min

11 - Stays at dim (never off)

4 - 5 min

8 - 15 min

1 - 0 min (disabled)*

4 - 45 min

2 - 15 min

5 - 60 min

3 - 30 min

1 - 5 sec

4 - 8 sec

7 - 15 sec

2 - 6 sec

5 - 9 sec

8 - 20 sec

3 - 7 sec

6 - 10 sec*

9 - 30 sec

1 - Normal*

4 - Low

2 - Off

5 - Phase Off (15-10-5 min)

3 - Medium

1 - 0 VDC

5 - 3 VDC

9 - 7 VDC

13 - 10 VDC*

2 - 1 VDC

6 - 4 VDC

10 - 8 VDC

3 - 1.5 VDC

7 - 5 VDC

11 - 9 VDC

4 - 2 VDC

8 - 6 VDC

12 - 9.1 VDC**

1 - 0 sec

3 - 15 sec*

1 - 0 sec

5 - 40 sec

2 - 10 sec*

6 - 50 sec

3 - 20 sec

7 - 60 sec

4 - 30 sec

1 - 0 VDC

5 - 3 VDC

9 - 7 VDC

13 - 10 VDC

2 - 1 VDC*

6 - 4 VDC

10 - 8 VDC

3 - 1.5 VDC**

7 - 5 VDC

11 - 9 VDC

4 - 2 VDC

8 - 6 VDC

12 - 9.1 VDC

1 - 0 sec

4 - 20 sec

7 - 50 sec

2 - 5 sec

5 - 30 sec*

8 - 60 sec

3 - 10 sec

6 - 40 sec

1 - 10%

4 - 40%

7 - 70%

10 - 100%*

2 - 20%

5 - 50%

8 - 80%

3 - 30%

6 - 60%

9 - 90%

1 - Set Now**

5 - 8 fc

9 - 48 fc

13 - 128 fc

2 - 0.1 fc

6 - 16 fc

10 - 64 fc

14- 192 fc

3 - 1 fc

7 - 24 fc*

11 - 80 fc

15 - 256 fc

4 - 4 fc

8 - 32 fc

12 - 96 fc

1 - Set Now**

5 - 8 fc

9 - 48 fc

13 - 128 fc

2 - 0.1 fc

6 - 16 fc

10 - 64 fc*

14- 192 fc

3 - 1 fc

7 - 24 fc

11 - 80 fc

15 - 256 fc

4 - 4 fc

8 - 32 fc

12 - 96 fc

* DEFAULT SETTING 

5-year limited warranty.  Full warranty terms located at: 

www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx 

Note: Specifications subject to change without notice.

Actual performance may differ as a result of end-user environment and application.

RENUNCIA:

Este documento ha sido traducido del inglés por razones de conveniencia. 

En el caso de cualquier inconsistencia entre el texto del documento en 

inglés y esta traducción, el texto en inglés controla.

Todas las marcas registradas a las que se hace referencia son propiedad 

de sus respectivos dueños. Marcas comerciales de Acuity Brands Las luces 

que están marcadas con el símbolo ® están registradas en los EE. UU. Y 

pueden estar registradas en otros países.

Summary of Contents for Sensor Switch WSX D

Page 1: ...n 40 ft coverage TOP VIEW 1 2 m 4 ft Small motion detection to 20 ft Large motion detection to 36 ft SIDE VIEW 0 18 27 36 9 ft 0 6 9 12 3 m TOP VIEW 36 30 20 10 0 ft 10 20 30 36 12 9 6 3 0 m 3 6 9 12...

Page 2: ...n 17 5 min 20 0 min 22 5 min 25 0 min 27 5 min 30 0 min 1 4 1 e g 6 flashes is default 10 min time delay e g press 5x to change to 7 5 min 2 3 e g press 2x for OccupancyTime Delay 2x 3x 4x 5x 6x 7x 11...

Page 3: ...efollowingoccupancytimedelay 11 LED Operation Indicatesbehaviorofdevice sLED 12 DualTechnology Microphonics Thesecondarymethodofoccupancydetectionthatallowsthesensortohearoccupants 13 Microphone Grace...

Page 4: ...OR 1 2 m 4 ft Detecci n de movimientos cortos a 20 ft Detecci n de movimientos grandes a 36 ft VISTA LATERAL 0 18 27 36 9 ft 0 6 9 12 3 m 36 30 20 10 0 ft 10 20 30 36 12 9 6 3 0 m 3 6 9 12 Detecci n d...

Page 5: ...min 12 5 min 15 0 min 17 5 min 20 0 min 22 5 min 25 0 min 27 5 min 30 0 min 1 ENCENDIDO APAGADO ENCENDIDO APAGADO 4 1 P ej 6 parpadeos indican por defecto un tiempo de retardo de 10 min P ej presione...

Page 6: ...ende cadainterruptor independientementedelestadodeocupaci n Unavezcumplido laslucesse reanudandespu sdeltiempoderetardodeocupaci n 11 Funcionamiento del led Indicaelcomportamientodelleddeldispositivo...

Page 7: ...s jusqu environ 20 pi D tection des mouvements importants 36 pi VUE LAT RALE 0 18 27 36 9 pi 0 6 9 12 3 m 36 30 20 10 0 pi 10 20 30 36 12 9 6 3 0 m 3 6 9 12 D tection des petits mouvements jusqu envir...

Page 8: ...n 30 0 min 1 MARCHE ARR T MARCHE ARR T 4 1 par exemple 6 clignotements correspond au d lai par d faut de 10 min par exemple appuyez 5 pour passer 7 5 min 2 3 2x 3x 4x 5x 6x 7x 11x 12x 10x 14x 15x 16x...

Page 9: ...re 9 R tablir les valeurs par d faut Ram netouteslesfonctions leurr glaged origine 10 Dur e minimum d allumage Dur eminimumd allumageinitialdeslampesapr schaquemisesoustension quelquesoitle statutd oc...

Reviews: