2.7 Optional 0-10V DC Dimming Controls Information 
2.7.1 

Certain control options available with the 

Wallpack® Full Cutoff LED luminaire have 0-10V DC 
dimming capabilities. General information for each is as 
follows: 

2.7.2 

For the field adjustable output (AO) module, the 

default setting is position 8 on the dial, which 
corresponds to 100% output. Output and can be 
adjusted by rotating the center dial. See tables 2-6 for 
additional dial settings and their corresponding outputs 
based on performance package. AO Tables are included 
on the last page of this installation manual. 

2.7.3 

For the occupancy sensor options (MASL & 

MASH), see luminaire spec sheet for specific mounting 
height information but in general the MASL option 
mounting height should not exceed 15’ and the MASH 
option mounting height should be between 15-30’ – 
Specific programming instructions for these devices is 
included in a separate document, included with the 
luminaire. 

2.7.4 

The part-night dimming (PND) option requires no 

special steps – the device comes preprogrammed. 

2.7.5 

For the NEMA twist-lock photocontrols (P3 and P7 

options), installed control nodes are sold separately and 
are not supported by Holophane product support. 

 
3 Maintenance 
3.1 Electrical Component Replacement 
3.1.1

 Disconnect power to the luminaire location before 

maintenance.  

3.1.2

 Open luminaire by loosening 6 heatsink screws 

and removing the heatsink from the electrical housing. 
Depending on the device being serviced/replaced it may 
be easiest to completely remove the heatsink from the 
electrical housing. Drivers and fuses are mounted to the 
heatsink, surge devices are mounted to the electrical 
housing. 

3.1.3

 Tag leads before disconnecting if they are not 

already labeled.  

3.1.4

 Replace components using Holophane approved 

replacement parts. 

3.1.5

 Re-connect electrical leads. See sections 2.3, 2.4, 

or 2.5 depending on luminaire configuration. 

3.1.6

 Reattach heatsink to electrical housing. See 

section 2.6. 
 

3.2 Heatsink - Optical Housing 

3.2.1 There are no user serviceable parts in the optical 
housing portion of the heatsink. 

 
4 Limited Warranty and Limitation of Liability 
 